Instruction Manual

10 | nVent.com/RAYCHEM
3/4 in lock nut
O-ring
Box plug
Install box plug using 3/8 in hex key.
19B
If used as a splice or tee connection
20
Plug in the light module in the terminal blocks
marked L and N as shown here.
(For simplicity the connected wires in the terminal
blocks are not shown in this step.)
Make sure
conductors
are not
exposed.
Watertight
conduit seal
3/4 in lock nut
1/2 in
(13 mm)
Power and ground wires
Conduit
drain
19A
Install conduit and fittings as shown. To
minimize loosening due to vibration, use
flexible conduit.
Pull in power and ground wires, strip
off 1/2 in (13 mm) of insulation, and
terminate.
nVent recommends the use of
a conduit drain to prevent water
condensation build-up.
If used as a power connection