Instruction Manual
nVent.com/RAYCHEM | 1
APPROVALS
Power Connection, Powered Splice, Powered Tee,
Dual Power Connection, Splice or Tee with Junction Box
and Light
DESCRIPTION
The nVent RAYCHEM JBM-100-L-A is a Type 4X-rated connection kit. It is
designed for use with nVent RAYCHEM BTV-CR, BTV-CT, QTVR-CT, XTV-CT,
KTV-CT, HTV-CT and VPL-CT industrial parallel heating cables. The kit can be
used to connect one, two, or three heating cables to power, to connect two
separate heat-trace circuits, or to splice or tee up to three heating cables. The
kit includes a plug-in light module that indicates when power is supplied to the
heating cable circuit.
Note: For two or more heating cables powered by a single circuit, the length of
each heating cable should not exceed the maximum allowable circuit length
published in the nVent RAYCHEM self-regulating cables design guide and the
total current of all heating cables on the circuit should equal no more than 80%
of the circuit breaker current rating.
This kit may be installed at temperatures as low as –40°F (–40°C). For easier
installation store above freezing until just before installation.
For technical support call nVent at (800)545-6258.
TOOLS REQUIRED
• Wire cutters
• Adjustable pliers
• Needle nose pliers
• Utility knife
• 1/4 in or smaller slotted
screwdriver
• Marking pen
• Wire stripper (for VPL-CT)
• Large slotted screwdriver
• 3/8 in hex key (required for splice and tee
connections)
ADDITIONAL MATERIALS REQUIRED
• Pipe strap • GT-66 or GS-54 glass cloth tape
OPTIONAL MATERIALS
• Recommended conduit drain: JB-DRAIN-PLUG-3/4IN P/N 278621-000
• Small pipe adapter for 1 in (25 mm) and smaller pipes:
Catalog number JBM-SPA P/N D55673-000
JBM-100-L-A
Installation Instructions
KIT CONTENTS
Item Qty Description
A 1 Stand assembly
B 2 Grommet plugs
C 1 Box plug, o-ring, and locknut
D 1 Cable lubricant
E 3 Core sealers
F 3 Green/yellow tubes
G 1 Box with terminal blocks
H 1 Lid
I 1 Spanner
J 1 Strain relief
K 1 JBL-100-R Plug-in module
A
D
C
B
H
G
F
E
I
J
K
(1)
®
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups E, F, G
Class III
CLI, ZN1, AEx em II T*
(1)
(2)
(JBM-100-L-A only) Ex eb mb IIC T* Gb
(2)
IECEx
JBM-100-L-A is IECEx certified for use with:
BTV-CR/BTV-CT: IECEx BAS 20.0011X
QTVR-CT: IECEx BAS 20.0013X
XTV-CT: IECEx BAS 20.0012X
KTV-CT: IECEx BAS 20.0014X
HTV-CT: IECEx PTB 21.0007X
VPL-CT: IECEx BAS 20.0008X
(3)
Class I Division 2 (Zone 2**), Groups A, B, C, D
Class I Zone 2 IIC
Ex eb mb IIC T* Gb; Class I Zone 1 AEx eb mb IIC T* Gb
Ex mb tb IIIC T*°C Db; Zone 21 AEx mb tb IIIC T*°C Db
*
For system Temperature Code, see heating cable or design documentation
(1)
Except VPL, HTV (FM approval only)
(2)
Except KTV-CT
(3)
For HTV-CT only ** Per CE Code Table 18
Hazardous Locations