Cut Sheet
Raychem
®
WinterGard
®
self-regulating heating
cables provide convenient, reliable freeze pro-
tection for a wide variety of professionally
installed residential and commercial water-pipe
and roof-and-gutter de-icing applications in
nonhazardous areas. This data sheet is
designed to assist in cable and accessory
selection and basic circuit design of pipe-
freeze-prevention applications.
Complete design guidelines, installation
instructions, and safety information are pro-
vided in the Commercial and Residential Self-
Regulating Heating Products Application and
Design Guide (H53585), the H900 Power
Connection Kit, the H908 Plug-in Power
Connection Kit, and the H921 120-V ground-
fault protected junction box.
For detailed information on roof and gutter de-
icing applications, please refer to the
WinterGard Wet Design, Installation and
Maintenance Guide (H56804).
16 AWG
bus wires
Conductive
core (black)
Insulated
jacket
(blue or red)
Tinned
copper braid
Water-proof
outer jacket
(black)
H612, H622 only
Construction
Pipe Applications
WinterGard systems must be installed correctly to
ensure proper operation and to prevent shock or fire.
Carefully read and follow the Commercial and Residential
Self-Regulating Heating Products Application and Design
Guide and the H900 series connection kit installation
instructions.
• Use only in ordinary (nonhazardous) areas. Do not
expose to any chemicals, oil or grease.
• In wet areas, use only WinterGard Wet.
• To minimize the danger of fire from sustained electrical
arcing if the heating cable is damaged or improperly
installed, and to comply with the requirements of Tyco
Thermal Controls, agency approvals, and national electri-
cal codes, ground-fault equipment protection must be
used on each heating cable branch circuit. Arcing may not
be stopped by conventional circuit protection.
• This selection guide does not take the place of the instal-
lation instructions included in the Commercial and
Residential Self-Regulating Heating Products Application
and Design Guide and in the H900 series accessory kits.
• System approvals and performance are based on the use
of only H900 series accessories with WinterGard heating
cables. These accessories must be used. Do not substi-
tute parts.
Water pipes in dry areas: H311/H611/H621
Water pipes in wet areas and refrigeration
condensate drains:
H612/H622
WinterGard
®
, WinterGard Plus
®
,
WinterGard Wet
®
Selection Guide
(for Pipe Freeze Protection Applications)
WARNING:
Product Specifications and Data
WinterGard
H311100
H311250
WinterGard Plus
H611050
H611100
H611250
WinterGard Plus
H621050
H621100
H621250
WinterGard Wet
H612050
H612100
H612250
H612500
H6121000
WinterGard Wet
H622050
H622100
H622250
H622500
H6221000
Service voltage 120 V 120 V 240 V 120 V 240 V
Power output at 40°F (W/ft) 3 6 6 6 6
Power output in refrigeration condensate
drains at 32°F (W/ft)
n/a n/a n/a 8 8
Weight per 100 ft (lb) 6 6 6 7 7
Nom. cable width (in) 0.380 0.380 0.380 0.415 0.415
Nom. cable thickness (in) 0.180 0.180 0.180 0.215 0.215
Bus wire gauge (AWG) 16 16 16 16 16
Braid wire gauge equivalent (AWG) 14 14 14 14 14
Insulating jacket type Modified polyolefin
Outer jacket type n/a n/a n/a Modified polyolefin
Maximum exposure temp. (°F) 150 150 150 150 150
Environment Use only in ordinary (nonhazardous) areas. Do not expose to any chemicals.
Agency approvals
*
1, 3 1, 3 1, 3 1, 2, 3 1, 2, 3
*
1 = UL System Listed 718K Pipe Heating Cable; 2 = UL System Listed 877Z De-Icing and Snow Melting Equipment; 3 = CSA Certified LR21133