Cut Sheet

MINIMUM BEND RADIUS
5/8 in (16 mm) 5/8 in (16 mm)
MAXIMUM CIRCUIT LENGTH IN FEET METERS
Start-up
temperature
Circuit breaker size
15 A 20 A 30 A 40 A*
GM-1XT and GM-1X at 120 volts 32°F (0°C) 100 (30) 135 (41) 200 (61)
20°F (–7°C) 95 (29) 125 (38) 185 (56) 200 (61)*
0°F (–18°C) 80 (24) 100 (30) 155 (47) 200 (61)*
GM-2XT and GM-2X at 208 volts 32°F (0°C) 190 (58) 250 (76) 380 (116)
20°F (–7°C) 180 (55) 235 (72) 355 (108) 380 (116)*
0°F (–18°C) 145 (44) 195 (59) 290 (88) 380 (116)*
GM-2XT and GM-2X at 240 volts 32°F (0°C) 200 (61) 265 (81) 400 (122)
20°F (–7°C) 190 (58) 250 (76) 370 (113) 400 (122)*
0°F (–18°C) 155 (47) 205 (62) 305 (93) 400 (122)*
GM-2XT and GM-2X at 277 volts 32°F (0°C) 215 (66) 290 (88) 415 (126)
20°F (–7°C) 200 (61) 265 (81) 400 (122) 415 (126)*
0°F (–18°C) 165 (50) 225 (69) 330 (101) 415 (126)*
* Only FTC-P power connection kits may be used with 40-A circuits.
BUS WIRES
16 AWG nickel-plated copper
BRAID / OUTER JACKET
Tinned-copper braid with fluoropolymer (-XT) or modified polyolefin (-X) outer
jacket
DIMENSIONS
Maximum width 0.54 in (14 mm)
Maximum thickness 0.24 in (6 mm)
NOMINAL WEIGHT
92 lb/1000 ft (137 kg/1000 m)
CONNECTION KITS
Raychem RayClic or FTC connection kits must be used with IceStop heating
cables. Refer to the Roof and Gutter De-Icing Design Guide (H56070) for proper
connection kit selection.
APPROVALS
877Z De-icing and
Snow-Melting
Equipment
Nonhazardous and Hazardous Locations
Class 1, Div. 2, Groups A, B, C, D*
* For GM-1XT and GM-2XT
-ws
GROUNDFAULT PROTECTION
The IceStop heating cables are UL Listed, CSA Certified, and FM Approved only
when used with the appropriate agency-approved Pentair Thermal Building &
Industrial Heat Tracing Solutions connection kits and accessories.
To minimize the danger of fire from sustained electrical arcing if the heating
cable is damaged or improperly installed, and to comply with the requirements
of Pentair Thermal Building & Industrial Heat Tracing Solutions, agency
certifications, and national electrical codes, ground-fault equipment protection
must be used on each heating cable branch circuit. Arcing may not be stopped by
conventional circuit protection. Many Raychem control and monitoring systems
meet the ground-fault protection requirement.
ICESTOP
EN-RaychemIceStopRoofGutterDeIcing-DS-H56428 02/16
2 / 3 Thermal Building &
indusTrial heaT Tracing soluTions