Cut Sheet

CIT1, GIT1, SIT6E
THERMAL MANAGEMENT SOLUTIONS
EN-ETICIT1GIT1SIT6E-DS-H58114 11/13
2 / 3
Sensors are easy to install and may be mounted up to 2000
ft (609 m) from a control panel. A combination of up to six
sensors may be used with a control panel to best match site
performance requirements.
For complete information describing applications,
installation and features, please contact your Pentair
Thermal Management representative or visit our web site
at www.pentairthermal.com.
GENERAL
Area of use
CIT–1 Gutters or pavement (in conjunction with GIT–1 or SIT–6E)
GIT–1 Gutters
SIT–6E Pavement
Heater hold-on time
CIT–1 None
GIT–1 None
SIT–6E 1 hour
Activation temperature 38°F (3.37°C)
CONNECTIONS
Circuit type NEC Class 2
Supply voltage 24 Vac (supplied by panel)
Output signal Voltage drop
Bus wire type 3-wire jacketed cable
Lead length Up to 2,000 ft (609 m) using 12 AWG 3-wire jacketed cable
Up to 500 ft (152 m) using 18 AWG 3-wire jacketed cable
ENVIRONMENTAL
Operating temperature –40°F to 160°F (–40°C to 71°C)
Storage temperature –50°F to 180°F (–45°C to 82°C)
ORDERING DETAILS
Catalog number Part number Description
CIT-1 512289-000 CIT-1 Snow sensor
GIT-1 126795-000 GIT-1 Gutter sensor
SIT-6E P000000112 SIT-6E Pavement snow sensor
LIMITED WARRANTY
ETI’s two-year limited warranty covering defects in workmanship and materials
applies.