Instruction Manual

1 in
1
Clearly cut off the end of
cable.
Score down and around
outer jacket 1 inch from
the end.
Remove the outer jacket.
Do not cut or damage
inner jacket. If damaged,
remove damaged section
and repeat step 1.
2
Remove exposed braid.
End Seal Installation for XL-Trace Edge -CR and -CT, and RaySol Heating Cables
Power connection box
3/4 in conduit
Waterproof thermal insulation
End seal box
Typical XL-Trace Edge Direct Buried Pipe Application
Power connection box
3/4 in conduit
End seal box
Typical RaySol Floor Warming Application
3
Insert end of cable in junction box.
Install junction box.
Firmly push end seal completely
onto heating cable (at least 1 1/2
inches). Some gel may ooze out.
Do not twist or try to remove the end
seal during or after insertion. Do not
reuse an end seal.
Note: The end seal is designed to
be installed only once; it cannot be
removed from the heating cable once
installed.
4
Attach Warning label
to junction box cover.
nVent.com/RAYCHEM
©2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specications without notice.
RAYCHEM-IM-H54743-FTCXC-EN-2111 PN 738279-000
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com
Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com
Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
cn.thermal.info@nVent.com
Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nVent.com