Cut Sheet

FTC HEAT SHRINKABLE CONNECTION KITS
THERMAL MANAGEMENT SOLUTIONS
EN-RaychemFTCheatshrinkablekits-DS-H58159 11/13
2 / 3
SPECIFICATIONS
Rated voltage 120–277 V
Maximum circuit breaker size 40 A
Maximum exposure temperature 150°F (65°C)
Minimum installation temperature 0°F (–18°C)
Enclosure rating NEMA 4X
APPLICABLE PRODUCTS
XL-Trace 5/8XL1-CR/CT and 5/8/12XL2-CR/CT
IceStop GM-1XT, GM-1X, GM-2XT and GM-2X
RaySol RaySol-1 and RaySol-2
APPROVALS
DESIGN AND INSTALLATION
For proper design and installation of a FTC connection kit, use the appropriate
product design guide and the installation instructions included with the
connection kit.
GROUNDFAULT PROTECTION
To minimize the danger of fire from sustained electrical arcing if the heating
cable is damaged or improperly installed, and to comply with the requirements
of Pentair Thermal Management, agency certifications, and national electrical
codes, ground-fault equipment protection must be used on each heating cable
branch circuit. Arcing may not be stopped by conventional circuit protection.
718K Pipe Heating Cable or
877Z De-Icing and Snow Melting
Equipment or 9J8 6 Radiant
Heating Cable
APPROVED
For XL-Trace heating cables
Certified with IceStop and
RaySol heating cables
With XL-Trace and IceStop heating cables
Hazardous locations:
Class I, Div 2. Groups A, B, C, D
GM-1XT and GM-2XT only