Installation Manual
4 Nuheat Cable Installation Guide
SECTION
FLOOR
HEATING
SYSTEM
Nuheat Cable
INSTALLATION
PREPARATION
INSTALLATION GUIDELINES
• Theinstallationofthisheatingproductshallbeinaccordancewiththe
manufacturer’s instructions and in accordance with the Canadian Electrical
Code Part 1 or the National Electrical Code
(
US
)
whichever is applicable.
• Thisequipmentshallbeinstalledonlybyqualiedpersonnelwhoarefamiliar
with the construction and operation of the apparatus and risks involved.
• Cautionshouldbetakentoguardagainstriskofelectricshock,reandbodily
injuryduringtheinstallationofthisequipment.
• NuheatCableshouldbeconnectedtoadedicatedelectricalcircuit.
• ItismandatorytoinstallaClass“A”GFCIorGFCIcircuitbreakerwitheach
Nuheat installation.
Nuheat thermostats are equipped with Class “A” GFCI protection.
• De-energizepowercircuitsbeforeinstallationorservicing.
• DONOTUSEsharptoolsorpowertoolstocleangroutlines.
• Nuheat’sCableGuidesaretheonlydevicesapprovedtosecureNuheatCable
onto the subfloor.
• IndicateontheelectricalpanelwhichcircuitisusedfortheNuheatCableSystem.
• SuboormustbepreparedinaccordancewithANSIspecications.
• NuheatCablecannotbeoverlapped,crossed,cut,shortenedormodied.
• TheentireheatingportionofNuheatCableandthemechanicaljointmustbe
secured to the floor and covered with self-leveling compound or thinset mortar.
• NuheatCableshouldbespacedatleast0.5inches
(
13mm
)
from any exposed
combustible surface and should never be installed in / on / under walls or in closets.
• Forconcreteslabsuboors,Nuheatrecommendsinsulatingtheslabpriorto
installing Nuheat Cable. Insulation will improve the upward heat transfer from
the cable to the flooring surface.
• TheNuheatCableSystemshouldneverbeinstalledoveranexpansionjoint.
• Theambientairtemperaturemustbeabove10°Cor50°FwhentheNuheat
Cable System is installed.
•NuheatCablemustnotextendbeyondtheroomorareainwhichitoriginates.
Cable is intended for indoor embedded floor heating applications in
the U.S., as well as in general use and wet locations
(
-W
) in Canada.
•Minimumspacingbetweenheatingcablerunis3”.
•Theminimumbendingradiusoftheheatingcableis0.5”(12mm).
•Keependsofheatingdevicesandkitcomponentsdrybeforeandduringinstallation.
•Thesheathofthisdeviceshallnotbeutilizedasagroundingconductor,but
must be bonded to the ground.
!
!