Cut Sheet
BUSBAR DISTRIBUTION SYSTEM 60mm system ClassiC
Spec-00507 L
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEBUSBAR SYSTEMS9
PROFILE TERMINAL, FOR DOUBLET BUSBAR
SECTIONS
Terminals for flat busbars and flexible copper busbars used to
either supply power to or draw power from the busbar system.
Cover caps are sold separately. Sold in sets of three terminals.
BULLETIN: HB2
Catalog Number
Description
Connection
Cross Section
(sq. mm)
Terminal
Space
W x H (mm) Side Supply (max.) Center Supply (max.) Qty. UL508 cURus
CSA
HB01185 For connecting flat busbars and flexible copper busbars 320–800 41 x 20 – 42 1600 A 1600 A 3 • • •
HB01906 For connecting flat busbars and flexible copper busbars 500–750 51 x 5 – 28 1600 A 1600 A 3 • • •
HB01907 For connecting flat busbars and flexible copper busbars 600–900 64 x 5 – 28 1600 A 1600 A 3 • • •
HB01936 For connecting flat busbars and flexible copper busbars 500–1000 51 x 20 – 42 1600 A 2000A 3 • • •
HB01911 For connecting flat busbars and flexible copper busbars 600–1200 64 x 20 – 42 1600 A 2000A 3 • • •
HB01934 For connecting flat busbars and flexible copper busbars 800–1600 81 x 20 – 42 1600 A 2500A 3 • • •
HB01935 For connecting flat busbars and flexible copper busbars 1000–2000 101 x 20 – 42 1600 A 2500A 3 • • •
PROFILE TERMINAL, FOR TRIPLET BUSBAR SECTIONS
Terminals for flat busbars and flexible copper busbars used to
either supply power to or draw power from the busbar system.
Cover caps are sold separately. Sold in sets of three terminals.
BULLETIN: HB2
Catalog Number
Description
Connection
Cross
Section (mm)
Terminal
Space
W x H (mm)
Side
Supply (max)
Center
Supply (max) Qty. UL508 cURus
CSA
HB01513 For connecting flat busbars and flexible copper busbars 320–860 41 x 23 – 45 1600 A 1600 A 3 • • •
HB01008 For connecting flat busbars and flexible copper busbars 500–1260 64 x 23 – 45 2000 A 2500 A 3 • • •
HB01186 For connecting flat busbars and flexible copper busbars 1200–3600 101 x 23 – 45 3200 A 3200 A 3 • • •
BUSBAR CONNECTOR, FOR SAMESIZE BUSBARS
Use to extend busbar lengths or to install a shipping split in a
modular enclosure assembly. Three units required for a 3-pole
section. Use HB01026 or HB01320 and HB01025 as a cover.
BULLETIN: HB2
Catalog Number
Description
Length
(mm)
System
Spacing
(mm)
Current
Capacity
(max.) Qty. UL508*
cULus
HB01166 12 – 20 X 5 / 10 55 5 – 10 630 A 3 •
HB01193 12 – 20 X 5 / 10 150 100 – 110 630 A 3 •
HB01990 20 – 30 X 5 / 10 40 9 – 20 630 A 3 • •
HB01823 20 – 30 X 5 / 10 40 13 – 20 630 A 3 • •
HB01141 20 – 30 X 5 / 10 95 50 – 60 630 A 3 • •
HB01886 20 – 30 X 5 / 10 150 100 – 110 630 A 3 • •
HB01827 Double-T Section 50 9 – 20 1600 A 3 • •
HB01145 Double-T Section 95 50 – 60 1600 A 3 • •
HB01829 Double-T Section 150 100 – 110 1600 A 3 • •
HB01274 Triple-T Section 95 50 – 60 2500 A 3 • •
HB01275 Triple-T Section 150 100 – 110 2500 A 3 • •
* Meets UL508 requirements when phase separators are installed.
PHASE SEPARATORS, FOR UL INSTALLATION OF END
TOEND BUSBAR CONNECTION, 3POLE
Satisfy the through-air arcing distances of the UL508 standard
when using end-to-end bubsar connectors, for the same-size
busbars.
BULLETIN: HB2
Catalog Number
Width (mm) For Use With Qty. UL508
cULus
HB01360 105 HB01166, HB01990, HB01823, HB01827 1 • •
HB01361 145 HB01141, HB01145, HB01274 1 • •
HB01362 200 HB01193, HB01886, HB01829, HB01275 1 • •