User Manual
Table Of Contents
- Warranty and Return Policy
- RECEIVING THE AIR CONDITIONER
- HANDLING AND TESTING THE AIR CONDITIONER
- HOW TO READ MODEL NUMBERS
- TECHNICAL INFORMATION
- Sequence of Operation
- Heating
- Cooling
- Thermostat
- Remote Access Control (optional)
- Head Pressure Control
- Contactor (115V 12000 BTU/Hr. Units only)
- Contactor (460V Units only)
- Overload (460V Units only)
- Phase Monitor
- 460V to 230V Transformer
- 115V to 10V or 230V to 10V Transformer (optional)
- 115V to 24V or 230V to 24V Transformer and Relay (optional)
- G521216GXXX Generic Schematic (actual unit options may vary)
- G52 All Other Generic 1-Phase Schematic (actual unit options may vary)
- G52 Generic 3-Phase Schematic (actual unit options may vary)
- G521216GXXX Generic Wire Diagram (actual unit options may vary)
- G52 All Other Generic 1-Phase Wire Diagram (actual unit options may vary)
- G52 Generic 3-Phase Wire Diagram (actual unit options may vary)
- INSTALLATION INSTRUCTIONS
- DIMENSIONAL DRAWINGS
- REMOTE ACCESS CONTROL (optional)
- OPERATING PARAMETERS
- ALARM PARAMETERS
- Remote Access Control Pin-out
- Schematic and Wiring Diagram for Remote Access Control
- G52 1-Phase Generic Schematic (actual unit options may vary)
- G52 Generic 3-Phase Schematic (actual unit options may vary)
- G52 Generic Wire Diagram for Remote Access Control (actual unit options may vary)
- G52 Generic 3-Phase Wire Diagram for Remote Access Control (actual unit options may vary)
- DIMENSIONAL DRAWINGS
- INSTALLATION INSTRUCTIONS WITH REMOTE ACCESS CONTROL
- MAINTENANCE
- Refrigerant Properties Chart (R 134a)
- Functional Data
- 8000 BTU/Hr. Unit Characteristics
- 12000 BTU/Hr. Unit Characteristics
- SERVICE DATA
- Components List
- TROUBLE SHOOTING
© 2018 nVent
89101404
- 15 -
DISPLAYING AND CHANGING PROGRAM VARIABLES
Access: To view and/or change parameters, press and hold the Prg and Sel buttons for greater than 5 seconds.
Press the up or down arrow buttons until “22” is displayed, then press Sel button. When “S-P” is displayed, press
Sel.
Navigation: Press up or down arrows to display sub-menus then press Sel to select the desired sub-menu. In the
sub-menu, use up or down arrows to display parameters for viewing or changing and press Sel. Use Prg button to
back out of menu levels as desired.
Adjust: Use the up or down arrows to change the parameter value then push Sel to save that setting. If Sel is not
pressed, the change to the value will not be saved. Navigate to and change other parameters as desired. When
nished, push Prg to back out of the sub-menus to the main menu.
NOTE: The display will revert to normal temperature display mode if no buttons are pressed
for 60 seconds.
OPERATING PARAMETERS
Parameter Default Value Range Description
r01 80 F 72 F to 120 F Cooling set-point
r02 7 F - Cooling differential
A04 50 F* 32 F to 60 F Heating set-point*
A05 7 F* - Heating differential*
Cooling turns on at r01 + r02, and off at r01
Heating turns on at A04, and off at A04 + A05
*Functional only on units with heater option
ALARM PARAMETERS
Parameter Default Value Description
P16 125 F High Temperature Alarm
P19 40 F Low Temperature Alarm
DISPLAYING TEMPERATURE SENSOR #2
Sensor number 2, the air outlet or condenser coil sensor, can be viewed at any time by pressing the up or down
arrow button on the front panel of the controller display. The display will revert to displaying temperature sensor
number 1 (the AC inlet temperature) after 60 seconds. Both sensors can also be read through the Ethernet and
USB connections.
COMPRESSOR RESTART TIME DELAY
A factory set 6 minute (360 second) restart delay exists to reduce residual back pressure before allowing the
compressor to restart. The compressor will stay off for the entire restart duration after the compressor is
disabled. A ashing “1” on the controller display will indicate the unit is in a compressor restart delay while calling
for cooling.
ALARM OUTPUT CONTACT
The Remote Access Control has a normally open dry contact alarm output with a resistive load rating of 250
VAC at 3 amps. Two yellow 18 AWG wires located at the back of the air conditioner provide a connection to this
output.