User Manual
Table Of Contents
- Warranty and Return Policy
- RECEIVING THE AIR CONDITIONER
- HANDLING AND TESTING THE AIR CONDITIONER
- HOW TO READ MODEL NUMBERS
- TECHNICAL INFORMATION
- Sequence of Operation
- Heating
- Cooling
- Thermostat
- Remote Access Control (optional)
- Head Pressure Control
- Contactor (115V 12000 BTU/Hr. Units only)
- Contactor (460V Units only)
- Overload (460V Units only)
- Phase Monitor
- 460V to 230V Transformer
- 115V to 10V or 230V to 10V Transformer (optional)
- 115V to 24V or 230V to 24V Transformer and Relay (optional)
- G521216GXXX Generic Schematic (actual unit options may vary)
- G52 All Other Generic 1-Phase Schematic (actual unit options may vary)
- G52 Generic 3-Phase Schematic (actual unit options may vary)
- G521216GXXX Generic Wire Diagram (actual unit options may vary)
- G52 All Other Generic 1-Phase Wire Diagram (actual unit options may vary)
- G52 Generic 3-Phase Wire Diagram (actual unit options may vary)
- INSTALLATION INSTRUCTIONS
- DIMENSIONAL DRAWINGS
- REMOTE ACCESS CONTROL (optional)
- OPERATING PARAMETERS
- ALARM PARAMETERS
- Remote Access Control Pin-out
- Schematic and Wiring Diagram for Remote Access Control
- G52 1-Phase Generic Schematic (actual unit options may vary)
- G52 Generic 3-Phase Schematic (actual unit options may vary)
- G52 Generic Wire Diagram for Remote Access Control (actual unit options may vary)
- G52 Generic 3-Phase Wire Diagram for Remote Access Control (actual unit options may vary)
- DIMENSIONAL DRAWINGS
- INSTALLATION INSTRUCTIONS WITH REMOTE ACCESS CONTROL
- MAINTENANCE
- Refrigerant Properties Chart (R 134a)
- Functional Data
- 8000 BTU/Hr. Unit Characteristics
- 12000 BTU/Hr. Unit Characteristics
- SERVICE DATA
- Components List
- TROUBLE SHOOTING
© 2018 nVent
89101404
- 33 -
8. Make sure the coils are clean. Then check evaporator “air in” and “air out” temperatures. If the
temperatures are the same:
» Possible loss of refrigerant
» Possible bad valves in the compressor
Repair or Replace
defective part
9. To check for a bad thermostat, turn power to the unit off. Remove the upper access panel and
place both thermostat wires onto one terminal (replace upper access panel for safety). This will
activate the switch in the thermostat. Turn the power on and if all impellers and the compressor
come on, the thermostat needs to be replaced.
SYMPTOMS AND POSSIBLE CAUSES - THERMOSTAT VERSION
SYMPTOM POSSIBLE CAUSE
Unit won’t cool
Clogged ns on coil(s)
Dirty lter
Impellers not running
Compressor not running
Compressor runs, but has bad valves
Loss of refrigerant
Compressor tries to start but won’t run
Low line voltage at start. Should be +/-10% rated voltage.
Compressor motor stuck
Bad contactor
Bad overload switch
Bad run/start capacitor
Unit blows breakers
Undersized breaker/fuse or not time delayed
Short in system
Getting water in enclosure
Drain plugged
Drain tube kinked
Enclosure not sealed (allowing humidity in)
Mounting gasket damaged
For additional technical support, contact nVent Equipment Protection at 800-896-2665.