INSTALLATION INSTRUCTIONS WITH REMOTE ACCESS CONTROL
1. Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See
HANDLING AND TESTING THE AIR CONDITIONER on page 19.
2. Using the mounting gasket kit provided with the unit, install gaskets to the air conditioner, see
Figure 2.
3. Mount air conditioner on enclosure taking care not to damage the mounting gasket. The
mounting gasket is the seal between the air conditioner and the enclosure. Avoid dragging the air
conditioner on the enclosure with the mounting gasket attached as this could cause rips or tears
in the gasket and risk losing the water tight seal.
4. Allow unit to remain upright for a minimum of ve (5) minutes before starting. CAUTION! Air
conditioner must be in upright position during operation.
5. Refer to the nameplate for electrical requirements. Wire the unit to a properly grounded power
supply. For 3 phase units, once power is applied, verify that phase monitor light is illuminated
which indicates correct electrical phasing. Electrical circuit should be fused with slow blow or
HACR circuit breaker.
6. Set controller setpoints for required cabinet temperature. Refer to DISPLAYING AND CHANGING
PROGRAM VARIABLES on page 15 for setpoint adjustment and operation.
88015593
Surface Mount
Figure 2