Datasheet

nVent.com | 1
INDUSTRY STANDARDS
ATEX Directive 94/9/EC
Sira 09ATEX3224U
Ex e IIC Gb
Ex tb IIIC Db IP 66
EN60079-0:2009
EN60079-7:2007
EN61241-0:2006
EN61241-1:2004
IECEx
IECEx SIR 09.0099U
Ex e IIC Gb
Ex tb IIIC Db IP 66
IEC 60079-0:2007-2010
IEC 60079-7:2006-2007
IEC 61241-0:2004
IEC 61241-1:2004
Type 4, 4X, 12; File No. E61997
cUL C22.2 No. 94 Listed; Type 4, 4X, 12; File No. E61997
NEMA/EEMAC Type 4, 4X, 12
IEC 60529, IP66
NEMA 4X enclosure (as a compNEMA 4X enclosure (as a component) is
suitable and complies with NEC Class I, Division 2, Groups A, B, C, D
assemblies*onent) is suitable and complies with NEC Class I, Division 2,
Groups A, B, C, D assemblies*
* with properly evaluated assemblies using terminal blocks and/or approved Class I, Division 1 or 2
(no arcs, sparks or hot surfaces) devices installed within the enclosure in accordance with NEC/
CEC requirements (reference NEC 2011 Article 501.10(B)(4) and NEC 2011 Handbook).
Note: this is not an Explosion Proof enclosure.

EC as well as IECEx standards for increased safety in housing electrical
components in Zone 1 and Zone 2 applications.
HOFFMAN ATEX Ex e enclosures are not intended for use in Explosion
Proof or ame-proof applications.
A
PPLICATION
Zonex enclosures deliver a robust solution for termination and junction
enclosure applications in potentially hazardous locations, including:
Petroleum and chemical processing
Water treatment processing
Pharmaceutical processing
Grain processing
SCOPE OF DELIVERY
Enclosure
Gland plate (assembled)
Mounting plate (assembled)
Assembly kit
Installation instruction
ATEX declaration of conformity
FEATURES
210 degree opening door that is easily removal by pulling clip style hinge pins
Fabricated and formed M5 threads for gland plate screws provide quick
and easy installation
SPECIFICATIONS
10 mm brass internal/external bonding provision
Type 316L stainless steel quarter-turn latch with double bit 3 mm insert

Continuous seal gasket on door and gland plate(s)
Mounting panel and hardware for bonding provisions included
Operating temperature range: –40 °C to +70 °C standard polyurethane
gasket; –55 °C to +180 °C optional silicone gasket

Fabricated from Type 316L stainless steel
2,5 mm thick individual welded-on top and bottom wall-mounting brackets
OPTIONS FOR MODIFICATION



Material changes: Type 304 stainless steel, painted mild steel or
aluminum
Gasket changes: high-temperature silicone gasket; operating temperature
range: –55 °C to +180 °C
Side-mount brackets available
Holes and cutouts
Paint
Ground bars
Terminal block installation and marking
Tagging (terminals, nameplates)
Accessory installations: drain/breathers and stopping plugs
ATEX - AND IECEX - CERTIFIED
Zonex Hinge Cover

Summary of content (2 pages)