Datasheet

HAZARDOUS LOCATION ENCLOSURES Hazardous Location EncLosurEs and accEssoriEs
nVent.com/HOFFMANSUBJECT TO CHANGE WITHOUT NOTICEHAZARDOUS LOCATIONS1
Spec-01042 C
Spec-01042
HAZARDOUS LOCATION BREATHER DRAINS
INDUSTRY STANDARDS
Ex e Breather Drains
Certified for Zone 1 or 2 areas
ATEX
Sira 13ATEX3354U
Ex e IIC Gb
Ex tb IIIC Db IP66
IECEx
IECEx SIR 13.0138U
Ex e IIC Gb
Ex tb IIIC Db IP66
cCSAus Certified Class 1 Zone 1, Ex e II, IP66, Type 4X
NEMA/EEMAC Type 4, 4X
IEC 60529, IP66
Maintain enclosure Type 4, 4X rating when properly installed
Ex d Breather Drains
Certified for Zone 1 or 2 areas
ATEX
ITS13ATEX17900X
Ex d IIC Gb
Ex e IIC Gb
Ex tb IIIC Db IP66
IECEx
IECEx ITS 13.0049X
Ex d IIC Gb
Ex e IIC Gb
Ex tb IIIC Db IP66
NEMA/EEMAC Type 4, 4X
IEC 60529, IP66
Maintain enclosure Type 4, 4X rating when properly installed
APPLICATION
Hazardous Location Breather Drains prevent moisture build-up
within hazardous approved enclosures while maintaining enclosure
UL Type rating. Drains are to be used when an enclosure is subject
to fluctuations in temperature which can lead to the formation of
condensation and a subsequent moisture build-up. These drains
allow air within an enclosure to breathe with the surrounding
atmosphere, preventing condensation and any potential damage to
electrical equipment.
FEATURES
• Reduce corrosion that can limit the life of internal electrical and
electronic components
• Prevent condensation when installations are subject to
fluctuations in temperature in hazardous locations
• Effectively drain any water present within the enclosure
• Minimize moisture build-up within the enclosure by allowing air
in the enclosure to breathe with surrounding atmosphere
• Position at the lowest point of an enclosure to ensure optimal
draining of any moisture
• Maintain enclosure’s UL Type rating when properly installed
• Available for Increased Safety (Ex e) and Flameproof (Ex d)
applications
SPECIFICATIONS
Ex e Breather Drains:
• Type 316 stainless steel with castellated nut and nitrile O-ring
• 10mm thread length
• Install in a clearance hole 0.5 to 1.0mm larger than major
diameter, or in a tapped hole
• Operating temperature of -58 F (-50 C) to 185 F (85 C)
Ex d Breather Drains:
• Type 316 stainless steel with silicone O-ring
• 16mm thread length
• Install in a tapped hole
• Operating temperature of -22 F (-30 C) to 302 F (150 C)
/
'

Bulletin: HlY
Catalog Number
AxBxC in. AxBxC mm Description Thread Type D (in.) D (mm) L (in.) L (mm) Weight (lbs.)
Weight (kg)
EXEBDM20SS6 1.57 x 1.57 x 0.98 40 x 40 x 25 Ex e M20 Breather Drain M20 1.13 28.7 .99 25.1 0.16 0.1
EXEBDM25SS6 1.57 x 1.57 x 0.98 40 x 40 x 25 Ex e M25 Breather Drain M25 1.41 35.8 1.30 33.0 0.27 0.1
EXDBDM20SS6 1.57 x 1.57 x 0.98 40 x 40 x 25 Ex d M20 Breather Drain M20 1.06 26.9 .99 25.1 0.18 0.1
EXDBDM25SS6 1.57 x 1.57 x 0.98 40 x 40 x 25 Ex d M25 Breather Drain M25 1.2 31.8 1.30 33.0 0.25 0.1

Summary of content (2 pages)