Cut Sheet

Free-Stand StainleSS Steel PreFerred-Cutout diSConneCtS PreferreD-cutout StainleSS Steel overview
PH 763.422.2211nVent.com/HOFFMAN diSConneCt 8
Spec-00385 O
PreFerred-Cutout overview
aPPliCation
Enclosures having the preferred cutout are sized for use with up to
200A disconnect switches and up to 400A circuit breakers unless
otherwisespecied.Thepreferredcutoutacceptsthesmaller
operating handle whose mounting hole centers are 4.688 in. apart.
Preferred cutouts are standard in mild steel wall-mount enclosures,
modular enclosures and some select large mild steel enclosures.
They are also present on all standard stainless steel offerings. 400
A (or greater) disconnect switches and 600 A (or greater) circuit
breakersrequirethe“Large”or“HighAmp”cutout.Thiscutout
accepts the larger operating handle whose mounting hole centers
are 6.500-in. apart. This large cutout is only available on PROLINE-
DD Disconnect Packages and Type 1 Free-Stand Enclosures.
Operator adapter for preferred cutouts must be ordered separately
tobeusedwithA21S,A28S4,A4SandWS2Denclosures.Preferred
cutouts are designed to house the following:
Allen-Bradley
•
Bulletin1494Uuniversaldisconnectswitcheswithange-mount
handles for either variable-depth or cable-operated mechanisms
• Bulletin1494Vdisconnectswitcheswithange-mountvariable-
depthoperatingmechanismsandBulletin1494Vange-mount
variable-depth operating mechanisms for circuit breakers
• Bulletin140Uexiblecableoperatingmechanismsfor140U
molded case circuit breakers
• Bulletin140Gexiblecableandvariable-depth,ange-mount,
molded case circuit breakers
• Bulletin1494Ccable-operateddisconnectswitcheswithange-
mount handles
•
Bulletin194RCcable-operatedange-mounthandlesforusewith
the NFPA 79 compliant 194R IEC rotary disconnect switches
Allen-Bradley Bulletin 1494V-R1, -R2 and -W2 operating handles and
Allen-Bradley Bulletin 1494F disconnect devices or Bulletin 1494D
circuit breaker operators will NOT t these enclosures.
ABB Controlsange-mountvariable-depthoperatingmechanisms
for disconnect switches and circuit breakers. Also the cable version
for circuit breakers.
Eaton Cutler-HammerTypeC361ange-mountvariable-depth
operating mechanisms with disconnect switches and Type C371
ange-mountvariable-depthoperatingmechanismsforcircuit
breakers.
General ElectricTypeSTDAangehandlesandvariable-depth
operating mechanisms for disconnect switches and circuit
breakers. Also SPECTRAFLEX cable operators for circuit breakers.
Siemens ITE MAX FLEX
®
ange-mountvariable-depthoperating
handles for circuit breakers.
SchneiderSquareD
®
Class9422disconnectswitcheswithange-
mount variable-depth operating mechanisms or cable mechanisms
andClass9422ange-mountvariable-depthoperatingmechanisms
or cable mechanisms for circuit breakers.
These enclosures will NOT accept Square D Class 9422 bracket-
mounted disconnect devices, Class 9422TG1 or TG2 devices.
ordering
Order the disconnect switch, operating handle and operating
mechanism separately. See Technical Information in the nVent
HOFFMANSpecier’sGuideforwirebendspaceavailablewhen
variousmanufacturers’disconnectswitchesareinstalled.Check
the enclosure dimension drawings to verify the chosen disconnect
switchwilltintheenclosure.