Cut Sheet
FREESTAND STAINLESS STEEL PREFERREDCUTOUT DISCONNECTS PreferreD-cutout StainleSS Steel overview
PH 763.422.2211nVent.com/HOFFMAN DISCONNECT 4
Spec-00139 L
PREFERREDCUTOUT OVERVIEW
APPLICATION
Enclosures having the preferred cutout are sized for use with
up to 200A disconnect switches and up to 400A circuit breakers
unless otherwise specified. The preferred cutout accepts the
smaller operating handle whose mounting hole centers are 4.688
in. apart. Preferred cutouts are standard in mild steel wall-mount
enclosures, modular enclosures and some select large mild steel
enclosures. They are also present on all standard stainless steel
offerings. 400 A (or greater) disconnect switches and 600 A (or
greater) circuit breakers require the “Large” or “High Amp” cutout.
This cutout accepts the larger operating handle whose mounting
hole centers are 6.500-in. apart. This large cutout is only available
on PROLINE-DD Disconnect Packages and Type 1 Free-Stand
Enclosures.
Operator adapter for preferred cutouts must be ordered separately
to be used with A21S, A28S4, A4S and WS2D enclosures. Preferred
cutouts are designed to house the following:
Allen-Bradley
•
Bulletin 1494U universal disconnect switches with flange-mount
handles for either variable-depth or cable-operated mechanisms
• Bulletin 1494V disconnect switches with flange-mount variable-
depth operating mechanisms and Bulletin 1494V flange-mount
variable-depth operating mechanisms for circuit breakers
• Bulletin 140U flexible cable operating mechanisms for 140U
molded case circuit breakers
• Bulletin 140G flexible cable and variable-depth, flange-mount,
molded case circuit breakers
• Bulletin 1494C cable-operated disconnect switches with flange-
mount handles
• Bulletin 194RC cable-operated flange-mount handles for use
with the NFPA 79 compliant 194R IEC rotary disconnect switches
Allen-Bradley Bulletin 1494V-R1, -R2 and -W2 operating handles and
Allen-Bradley Bulletin 1494F disconnect devices or Bulletin 1494D
circuit breaker operators will NOT fit these enclosures.
ABB Controls flange-mount variable-depth operating mechanisms
for disconnect switches and circuit breakers. Also the cable version
for circuit breakers.
Eaton Cutler-Hammer Type C361 flange-mount variable-depth
operating mechanisms with disconnect switches and Type C371
flange-mount variable-depth operating mechanisms for circuit
breakers.
General Electric Type STDA flange handles and variable-depth
operating mechanisms for disconnect switches and circuit
breakers. Also SPECTRAFLEX cable operators for circuit breakers.
Siemens ITE MAX FLEX
®
flange-mount variable-depth operating
handles for circuit breakers.
Schneider Square D
®
Class 9422 disconnect switches with flange-
mount variable-depth operating mechanisms or cable mechanisms
and Class 9422 flange-mount variable-depth operating
mechanisms or cable mechanisms for circuit breakers.
These enclosures will NOT accept Square D Class 9422 bracket-
mounted disconnect devices, Class 9422TG1 or TG2 devices.
ORDERING
Order the disconnect switch, operating handle and operating
mechanism separately. See Technical Information in the Hoffman
Specifier’s Guide for wire bend space available when various
manufacturers’ disconnect switches are installed. Check the
enclosure dimension drawings to verify the chosen disconnect
switch will fit in the enclosure.