Cut Sheet
Hazardous Location EncLosurEs Hazardous Location EncLosurEs and accEssoriEs
nVent.com/HOFFMANSUBJECT TO CHANGE WITHOUT NOTICEHazardous Locations1
Spec-00225 H
Spec-00225
nEMa typE 9
industry standards
UL Class II Division 1 and 2 Group E, F and G locations
UL File No. E67456
NEMA/EEMAC Type 9
CSA certified for Class II Division 1 and 2 Group E, F and G locations
IEC 60529, IP60
CSA File No. 42186
appLication
For use in Class II Division 1 and 2 locations as defined in Article
500 of the National Electrical Code as having the presence of
combustible dusts.
spEciFications
•
0.19-in. (5-mm), .25-in. (6-mm) and .38-in. (10-mm) steel plate
•
Ends are .38-in. (10-mm) steel plate to provide a minimum of 3.50
full threads for conduit sizes through 2.00 in. (51 mm). (Class II
enclosures must have minimum of 3.50 full threads at all conduit
entrances. NEMA requires conduit entrances to be in top and/
or bottom of enclosure. Tapped holes for conduit should have
tapered pipe threads.)
• Covers are .25-in. (6-mm) thick to allow mounting of NEMA 9
pushbuttons and pilot lights, which require threaded holes (3/4-
14 NPSM thread)
• Heavy duty cover hinges on enclosures when “A” is 20.00 in. (508
mm) or more
• Fiber gasket, mechanically attached to cover, assures dust-tight
enclosure
• Weldnuts or collar studs provided for mounting optional panel
FinisH
ANSI 61 gray polyester powder finish inside and out over pretreated
surfaces.
accEssoriEs
Panels for Type 1 Enclosures and Small Type 3R Enclosures
Panels for Type 3R, 4, 4X, 12 and 13 Enclosures
Terminal Block Kit Assembly for Junction Boxes
Terminal Block Kit Assembly for Type 4, 12, 13 Enclosures
Hazardous Location LED Lights, Strip
Hazardous Location LED Light, CAN
Bulletin: A9