Cut Sheet
Blocks AND tERMINAls PowER tERMINAls
Spec-01140 F
EQUIPMENT PROTECTION PowER AND GRouNDING coNNEctIvIty 48
Unit Dimensions
Catalog Number Depth D (in.) Height H (in.) Width W (in.) A (in.) Unit Weight (lb.) Qty.
SBLT800 2.95 8.10 4.53 4.25 2.40 1
Max Current Rating, IEC Max Current Rating, UL/CSA
Short Term
Withstand
Current (Icw) 1s
Peak Short
Circuit Current
(Ipk)
Short Circuit
Current Rating
(SCCR)
Max Working
Voltage, IEC (Ui)
Max Working
Voltage, UL (Vin)
1,250 A 760 A 57.6 kA 75 kA 100 kA
1,000 VAC
1,500 VDC
1,000 VAC/DC
Number of
Stud Connections
Stud Connection
Conductor Width
Stud Connection Compact
Stranded Wire Size
Stud Connection
Wire Size
Number of Tunnel
Connections
Tunnel Connection Compact
Stranded Wire Size
Tunnel Connection
Wire Size - Ferrule
Tunnel Connection
Wire Size
2
(2) 20 – 40 mm
(1) 50 – 80 mm
(2) 35 – 300 mm² (2) #1 - 500 kcmil 2 (2) 95 – 240 mm² (2) 50 – 185 mm² (2) 3/0 – 500 kcmil
Derating according to Ambient* Temperature (°F) to maintain working temperature of 185°F
Ambient
Temperature
(°F)
86° 95° 104° 113° 122° 131° 140° 149° 158° 167°
Derating
Coefficient (d)
1 1 1 0.94 0.88 0.82 0.75 0.67 0.58 0.47