Cut Sheet
Blocks AND tERMINAls PowER Blocks
Spec-01140 F
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPowER AND GRouNDING coNNEctIvIty39
two cABlEs to ERIFlEX FlEXIBAR/INsulAtED PowER BRAID PowER Block
INDustRy stANDARDs
FEAtuREs
line side
conductor connections
Design allows for visual inspection of conductor and
confirmation of connection
Voltage detection and measurement connection
95% fill ratio
Halogen free
FINIsh
+
:
'
Unit Dimensions
Catalog Number Material Depth D (in.) Height H (in.) Width W (in.) Unit Weight (lb.) Qty.
SBF2C400 Copper, Thermoplastic 3.23 5.76 1.63 1.67 1
SBF2C400AL Aluminum, Thermoplastic 3.23 5.76 1.63 0.74 1
Catalog Number
Max Current Rating,
ERIFLEX FLEXIBAR, IEC
Max Current Rating,
Insulated Power Braid, IEC
Max Current
Rating, UL
Peak Short Circuit
Current (Ipk)
Short Circuit Current
Rating (SCCR)
Max Working
Voltage, IEC (Ui)
Max Working
Voltage, UL (Vin)
SBF2C400 560 A 500 A 335 A 51 kA 100 kA
1,000 VAC
1,500 VDC
1,000 VAC/DC
SBF2C400AL 550 A 480 A 335 A 51 kA 100 kA
1,000 VAC
1,500 VDC
1,000 VAC/DC
Catalog Number
Line Side Number
of Connections
Line Side Insulated
Power Braid Cross Section
Load Side Number
of Connections
Load Side Compact
Stranded Wire Size
Load Side Stranded
Wire Size - Ferrule
Load Side Wire Size
SBF2C400 1 100 mm² 2 (2) 35 - 120 mm² (2) 35 - 120 mm² (2) #2 – 250 kcmil
SBF2C400AL 1 100 mm² 2 (2) 35 - 120 mm² (2) 35 - 120 mm² (2) #2 – 250 kcmil
Derating according to Ambient* Temperature (°F) to maintain working temperature of 185°F
Ambient
Temperature (°F)
86° 95° 104° 113° 122° 131° 140° 149° 158° 167°
Derating
Coefficient (d)
1 1 1 0.94 0.88 0.82 0.75 0.67 0.58 0.47
*environment around the terminal blocks inside the enclosure