Cut Sheet

Blocks AND tERMINAls PowER Blocks
Spec-01140 F
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPowER AND GRouNDING coNNEctIvIty35

Catalog Number
Line Side Number
of Connections
Line Side Compact
Stranded Wire Size
Line Side
Solid Wire Size
Load Side Number
of Connections
Load Side Compact
Stranded Wire Size
Load Side Stranded
Wire Size - Ferrule
Load Side
Solid Wire Size
SB80 1
6 – 16 mm²
#16 – #4
2.5-6 mm
2
#16-#10
1
6 - 16 mm²
#16 – #4
6 - 16 mm²
2.5-6 mm
2
#16-#10
SB80AL 1
6 – 16 mm²
#16 – #4
2.5-6 mm
2
#16-#10
1
6 – 16 mm²
#16 – #4
6 - 16 mm²
2.5-6 mm
2
#16-#10
SB125 1
10 – 35 mm²
#8 – 1/0
1
10 – 35 mm²
#8 – 1/0
10 - 35 mm²
SB125AL 1
10 – 35 mm²
#8 – 1/0
1
10 – 35 mm²
#8 – 1/0
10 - 35 mm²
SB160 1
35 – 70 mm²
#2 – 3/0
1
35 - 70 mm²
#2 – 3/0
35 - 70 mm²
SB160AL 1
35 – 70 mm²
#2 – 3/0
1
35 - 70 mm²
#2 – 3/0
35 - 70 mm²
SB250 1
35 – 120 mm²
#6 – 250 kcmil
1
35 - 120 mm²
#6 – 250 kcmil
35 - 120 mm²
SB250AL 1
35 – 120 mm²
#6 – 250 kcmil
1
35 - 120 mm²
#6 – 250 kcmil
35 - 120 mm²
SB400 1
95 – 240 mm²
3/0 – 400 kcmil
1
95 - 240 mm²
3/0 – 400 kcmil
95 - 240 mm²
SB400AL 1
95 – 240 mm²
3/0 – 400 kcmil
1
95 - 240 mm²
3/0 – 400 kcmil
95 - 240 mm²
SB630 1
240 – 500 mm²
400 – 1,000 kcmil
1
240 - 500 mm²
400 – 1,000 kcmil
240 - 500 mm²
SB630AL 1
240 – 500 mm²
400 – 1,000 kcmil
1
240 - 500 mm²
400 – 1,000 kcmil
240 - 500 mm²

Derating according to Ambient* Temperature (°F) to maintain working temperature of 185°F
Ambient
Temperature
(°F)
86° 95° 104° 113° 122° 131° 140° 149° 158° 167°
Derating
Coefficient (d)
1 1 1 0.94 0.88 0.82 0.75 0.67 0.58 0.47
*environment around the terminal blocks inside the enclosure