Cut Sheet

Blocks AND tERMINAls two- AND FouR-PolE DIstRIButIoN Blocks
Spec-01140 F
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPowER AND GRouNDING coNNEctIvIty23
two- AND FouR-PolE DIstRIButIoN Blocks, 100/125/160 AMP
FEAtuREs
 
 
 
 
 
 
 
BD two PolE DIstRIButIoN Block, 100/125 A
INDustRy stANDARDs



FEAtuREs
 
 Protection cover and insulating screens are transparent
 
 
 
 
 
 Halogen free
 
:
+
'
Unit Dimensions
Catalog Number Depth D (in.) Height H (in.) Width W (in.) Unit Weight (lb.) Qty.
BD100125A 1.97 1.97 3.70 0.35 1
BD100125AL 1.97 1.97 6.38 0.60 1

Catalog Number Max Current Rating, IEC Short Term Withstand Current (Icw) 1s Peak Short Circuit Current (Ipk) Max Working Voltage, IEC (Ui)
BD100125A 125 A 4.5 kA 30 kA 690 V
BD100125AL 125 A 4.5 kA 25 kA 690 V

Catalog Number
Line Side Number
of Connections
Line Side Compact
Stranded Wire Size
Line Side Stranded
Wire Size - Ferrule
Load Side Number
of Connections
Load Side Compact
Stranded Wire Size
Load Side Stranded
Wire Size - Ferrule
BD100125A 1 10 – 35 mm² 10 – 35 mm² 6 (5) 2,5 – 6 mm² (1) 10 – 25 mm² (5) 1,5 – 6 mm² (1) 6 – 16 mm²
BD100125AL 1 10 – 35 mm² 10 – 35 mm² 14 (11) 2,5 – 6 mm² (3) 10 – 25 mm² (11) 1,5 – 6 mm² (3) 6 – 16 mm²

Derating according to Ambient* Temperature (°F) to maintain working temperature of 185°F
Ambient
Temperature
(°F)
86° 95° 104° 113° 122° 131° 140° 149° 158° 167°
Derating
Coefficient (d)
1 1 1 0.94 0.88 0.82 0.75 0.67 0.58 0.47
*environment around the terminal blocks inside the enclosure