Cut Sheet

Blocks AND tERMINAls two- AND FouR-PolE DIstRIButIoN Blocks
Spec-01140 F
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPowER AND GRouNDING coNNEctIvIty19
tD coMPAct FouR PolE DIstRIButIoN Block, 40 A
INDustRy stANDARDs



FEAtuREs
 
 Protection cover and insulating screens are transparent
 
 
 
 
 
 Halogen free
 
sPEcIFIcAtIoNs
 
:
'
+
Unit Dimensions
Catalog Number Depth D (in.) Height H (in.) Width W (in.) Unit Weight (lb.) Qty.
TD40A 1.97 3.54 3.94 0.73 1

Max Current Rating, IEC Short Term Withstand Current (Icw) 1s Peak Short Circuit Current (Ipk) Max Working Voltage, IEC (Ui)
40 A 4.5 kA 22 kA 500 V

Line Side Number
of Connections
Line Side Compact
Stranded Wire Size
Line Side Stranded
Wire Size - Ferrule
Load Side Number
of Connections
Load Side Compact
Stranded Wire Size
Load Side Strande
Wire Size - Ferrule
2 6 – 16 mm² 4 – 10 mm² 11 (15) 1,5 – 4 mm² (15) 0,75 – 4 mm²

Derating according to Ambient* Temperature (°F) to maintain working temperature of 185°F
Ambient
Temperature
(°F)
86° 95° 104° 113° 122° 131° 140° 149° 158° 167°
Derating
Coefficient (d)
1 1 1 0.94 0.88 0.82 0.75 0.67 0.58 0.47
*environment around the terminal blocks inside the enclosure