Cut Sheet
Blocks AND tERMINAls two- AND FouR-PolE DIstRIButIoN Blocks
Spec-01140 F
EQUIPMENT PROTECTION PowER AND GRouNDING coNNEctIvIty 18
two- AND FouR -PolE DIstRI ButIoN Bloc ks
two- AND FouR-PolE DIstRIButIoN Blocks, 40/80/100 AMP
FEAtuREs
Self extinguishing: UL94 V-0
Safe connections
Halogen Free
BD two PolE DIstRIButIoN Block, 40 A
INDustRy stANDARDs
FEAtuREs
Protection cover and insulating screens are transparent
Halogen free
:
+
'
Unit Dimensions
Catalog Number Depth D (in.) Height H (in.) Width W (in.) Unit Weight (lb.) Qty.
BD40A 1.97 1.97 5.12 0.49 1
Max Current Rating, IEC Short Term Withstand Current (Icw) 1s Peak Short Circuit Current (Ipk) Max Working Voltage, IEC (Ui)
40 A 4.5 kA 22 kA 500 V
Line Side Number
of Connections
Line Side Compact
Stranded Wire Size
Line Side Stranded
Wire Size - Ferrule
Load Side Number
of Connections
Load Side Compact
Stranded Wire Size
Load Side Stranded
Wire Size - Ferrule
2 6 – 16 mm² 4 – 10 mm² 15 (15) 1,5 – 4 mm² (15) 0,75 – 4 mm²
Derating according to Ambient* Temperature (°F) to maintain working temperature of 185°F
Ambient
Temperature
(°F)
86° 95° 104° 113° 122° 131° 140° 149° 158° 167°
Derating
Coefficient (d)
1 1 1 0.94 0.88 0.82 0.75 0.67 0.58 0.47
*environment around the terminal blocks inside the enclosure