Cut Sheet

VB/VFVERTICAL STEEL SURFACE
REQUIRED TOOLS
VERTICAL STEEL SURFACE
Connection of vertical cable to vertical flat steel surface
or to side of vertical or horizontal steel pipe.
A test weld should be made to check the possibility
of burn through on thin sections or thin wall pipe.
Concentric stranded copper cable listed.
Cable to steel pipe. Add pipe orientation and nominal
pipe size to flat surface mold part number. Examples:
VFC-2G-V6, 2/0 conductor to vertical 6" pipe.
VFC-1Y-H4, #1 conductor to horizontal 4" pipe
Bold letter in mold part number is the price key.
Cable Cleaning Brush T313 or T314
Rasp T321
Slag Removal Spade B136A or B136B
Mold Cleaning Brush T394
Torch Head T111
See Section A
CABLE MOLD WELD
SIZE PART NO. METAL
4VBC-1L 65
2 SOL VBC-1T 65
2VBC-1V 65
1VBC-1Y 90
1/0 VBC-2C 115
2/0 VBC-2G 115
3/0 VBC-2L 150
4/0 VBC-2Q 150
250 VBC-2V 200
300 VBC-3A 200
350 VBC-3D 250
500 VBR-3Q 2-150
CABLE MOLD WELD
SIZE PART NO. METAL
4VFC-1L 65
2 SOL VFC-1T 65
2VFC-1V 65
1VFC-1Y 90
1/0 VFC-2C 150
2/0 VFC-2G 150
3/0 VFR-2L 200
4/0 VFR-2Q 200
250 VFR-2V 200
300 VFR-3A 250
350 VFF-3D 2-150
500 VFF-3Q 2-200
*See VF connection to pipe on page 3-8
VB
Cable down to
vertical steel surface
VF
Cable up to vertical
steel surface
SUGGESTED TOOLS
ACCESSORIES
Handle Clamps L160 for C and R Price Key Molds
L159 for F Price Key Molds
Flint Ignitor T320 (Included with handle clamp
but also available separately)
TYPE VB
TYPE VF*
3-9
Ph: 1-800-677-9089