Rod Size: 1/4"
A: 1.300"
Static Load: 95 lb
ADDITIONAL PRODUCT DETAILS
Uses Powers Fasteners, Inc. part number 50378.
Static load was established based on a 1-1/8” (28.6 mm) embedment depth and 3,000 psi (20.68 Mpa) normal-weight
concrete. For variations in embedment and material please consult www.powers.com. 󰾬
Pre-assembled drive pin from Powers Fasteners, Inc. works with Powers® C4CZ, Simpson® GCN-MEPKT, SPIT® P1000,
P200, P2201, P3500 / PA3500, P35s, P45, P60, P7201, Sniper; Ramset® 721, Cobra, D45 / D60 / D60L, M70, SA270, T3SS,
TS750P, TS60P, Viper; Hilti® DX35, DX350 / DX351 / DX36M, DX100 / DX200, DX460, DXA40, DXA41,󰾬 DXE72 / DX400;
Würth® Diva-1, BST-1, BST-2 or equivalent nailers.
For shot-fired supports in seismic design category D, E, or F, maximum load is the lesser of 90 lb (400 N) or the published
load.
Exempt from seismic design when supporting conduits less than 2-1/2” (64 mm) trade size, regardless of Ip.
Refer to DeWalt Engineered by Powers Ceiling Clip Assembly ICC-ES Evalution Report ESR-2024 for the allowable load
ratings in various substrate material and embedment depths.
DIAGRAMS
WARNING
nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials.
Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper
installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause
product malfunction, property damage, serious bodily injury and death and/or void your warranty.