Instructions / Assembly
Connecting the Low Voltage Wiring
Ideally, you will run the wiring and make all the wiring
connections after you have completed the tubing
system. Of course, the inlet wiring must be run at the time
the inlet tubing is threaded through the walls.
Run the low voltage wiring along the trunk line; at
approximately 12˝-18˝ intervals, use electrical tape to
secure the wire to the tubing. Then, run wiring along the
branch lines from the inlet lines to the trunk line. Also
secure this wiring with electrical tape.
At the joint of the inlet line and the branch line, make a two-wire
connection. Use wire nuts to make the connections and
insulate each connection with electrical tape.
At the junction of every branch line and the trunk line, cut
the trunk line wire and connect it to the branch
line wire. Connect this wiring in groups of 3–one branch
wire, one in-coming trunk line wire and one
outgoing trunk line wire. Insulate all wire connections with
electrical tape.
Complete all wiring connections up to the power unit’s
intake access hole. You will make this connection when
you mount and connect the power unit. If, for some
reason, you want to connect the wire as you go along,
make the same two-wire and three-wire connections
where required.
Assembling a Basement Trunk Line
Basically, the tubing network is assemble the same way for a
basement installation. Begin the trunk line at the farthest inlet
line from the power unit. Measure and cut the inlet tubing to the
length required to align the trunk line with the joists or ceiling.
Cement the inlet tubing and connect at 90° elbow. Then, run
the trunk line until you reach a branch line junction point.
29