User's Manual

Location 2, events to report to central station
Phone fault detected. This location has 16 segments.
Note:
Reporting must be enabled in the control panel for this location to function.
This location selects the partitions to include when reporting to the central station. To exclude any partition
from reporting, turn off the LED corresponding to that particular partition number. Enter the numbers of the
partitions to include for each type of report found in segments 1 through 16. Factory default is all partitions on
for segment 1; all partitions off for segments 2 to 16.
Table 7 describes the segment options.
Table 7. Location 2 options
Location 3, special events to report to central station
Phone fault detected. This location has 8 segments.
This location selects the partitions to include when reporting special events to the central station. To exclude
any partition from reporting, simply turn off the LED corresponding to that particular partition number. Enter
the numbers of the partitions to include for each type of report found in segments 1 through 4. Factory default
is all partitions off for segment 1 and 3; all partitions on for segments 2 and 4. Segments 5 to 8 are reserved
for future use.
Table 8 describes the segment options.
Table 8. Location 3 options
Segment Description
1 Alarms
2 Open/close
3 Bypass
4 Zone trouble
5 Power trouble (AC failure or low battery)
6 Siren and telephone fault
7 Test reports
8 Program, download, and log full
Segment Description
9 Tampers
10 Short circuit and ground fault
11 Sensor lost
12 Sensor low battery
13 Expander trouble
14 Failure to communicate
15 Zone activity monitor
16 Reserved for future use.
Segment Description
1 Alarm restores
2 Telephone fault
Segment Description
3 Start download
4 Fail to communicate, data lost