Manual
DigiGate Profibus 
NOVUS AUTOMATION  9/10 
Control Register 
Bit15  Bit14  Bit13  Bit12  Bit11  Bit10  Bit9  Bit8  Bit7  Bit6  Bit5  Bit4  Bit3  Bit2  Bit1  Bit0 
RD  WD  WT1  WT0  res  res  RCD1  RCD0  SA7  SA6  SA5  SA4  SA3  SA2  SA1  SA0 
•  Bit 15 – RD (Request Data Valid) - This bit is inverted by the Profibus master when valid data are to be 
read. When the gateway is in not reset state (RS0=0, RS1=0), the master must mandatorily invert this bit for 
resetting the gateway. Otherwise the inversion will not be necessary for updating the data; however, it will be 
useful to confirm updating. 
•  Bit 14 – WD (Write Data) - This  bit is  inverted  by  the  Profibus master  when a  writing  operation  is  to  be 
executed in the gateway. 
•  Bit 13 e Bit 12 – WT1, WT0 (Write Type) – the Profibus master will indicate through these bits the type of 
writing associated to bit 14. 
  00 - the entire table shall be transferred to the Modbus network. 
01 - only those table  values shall be  transferred  to the  Modbus which have  been changed since  the last 
writing operation. 
10 - a writing operation will be executed in the table, but no value shall be sent to the Modbus network. 
  11 - reserved 
•  Bit 11 – reserved 
•  Bit 10 – reserved 
•  Bit  9,  Bit  8  -  RCD1,  RCD0  (Request  connect/disconnect)  –  A  user  disconnected  block  will  remain 
disconnected until a block reconnection request is sent or until a DigiGate is reset. 
Request  for disconnection / reconnection – will be  executed  by a request  for writing through WD 
(has higher priority than writing in table) 
00 - No operation 
01 - Disconnect device 
10 - Reconnect device 
11 - Reserved 
•  Bit 7 a Bit 0 – SA7 to SA0 (Slave Adress) 
  Slave address related to Bit9 and Bit8 
Hints for Use: 
•  Use the bits of the status and control registers for correct operation of the device. 
•  Before performing a writing operation, it is recommended to check the state of the Profibus connection by 
changing the RD pin (control register) and later checking the DV pin (status register). 
•  After  having  established  the  connection  to  the  Profibus  network,  execute  the  entire  output  table  writing 
(WT1=0 and WT0=0) as the first writing operation. 
•  The best way of assuring that a writing operation has been executed correctly is verifying the registers after 
the writing operation is done. 










