•  Bit 8 – EQ (Error Qualifier) – valid for “Error Type” (bits 11, 10 and 9) different from 000 
  0 – one slave presenting a failure 
  1 – more than one slave with failure 
In case we have more than one reading command for each Modbus slave: 
  0 – one reading command with failure 
  1 – more than one reading command with failure 
•  Bit 7 a Bit 0 – AN7 to AN0 (Address/Number) – slave address presenting a failure (if there is only 1 slave 
with failure) or number of slaves with failure. 
Note: The initial status of all bits of the status register is zero. 
Writing Table: 
Figure 9 – Writing in the Modbus slaves by the Profibus master 
The Writing Table or Output Table contains the values that are to be written in the registers of the Modbus network 
(according to configuration), besides a control register (1st position of the table). It is aligned to the field of data sent from 
the Profibus master to the DigiGate. However, the values of this table will correspond to the values sent by the Profibus 
master only if there is a request by the control register. Its format is as follows: 
Position 0 
Control Register– in details below 
Position 1 
Value to be written in the equipment register in the Modbus network 
Position 2 
Value to be written in the equipment register in the Modbus network 
................. 
....................................................................................................... 
Position 121 
Value to be written in the equipment register in the Modbus network 
At the equipment configuration the table positions are associated to the Modbus registers for which writing shall be 
allowed. All positions are values of 16 bits. The table size is preset (122 words of 16 bits), the size of the data block 
received from the Profibus network, however, is configurable and may not correspond to the table in its totality. 