User Manual

7
Simplex 4010 NION Installation/Operation Manual Version 2 Document 51998 Rev. A1 03/26/03
Foreword
The contents of this manual are important and must be kept in close proximity of the UniNet™ Facilities Monitoring
System. If building ownership is changed, this manual and all other testing and maintenance information must also
be passed to the current owner of the facility. A copy of this manual was shipped with the equipment and is also
available from the manufacturer.
NFPA Standards
National Fire Protection Association Standards 72 (NFPA 72).
National Electric Code (NFPA 70).
Life Safety Code (NFPA 101).
Underwriters Laboratories U.S. Documents
UL-864 Control Units for Fire Protective Signaling Systems (Ancillary monitoring only).
Other
Requirements of the Local Authority Having Jurisdiction (LAHJ).
WARNING:WARNING:
WARNING:WARNING:
WARNING: Improper installation, maintenance, and lack of routine testing could result in system malfunction.
Introduction
The NION-Simplex 4010 is a plug-in component of the UniNet™ 2000 Workstation. It allows a workstation to
view events and other data originating from a Simplex 4010 panel.
UniNet™ consists of graphical workstations monitoring and controlling, local or remote twisted pair or fiber optic
networks. Remote network monitoring is achieved through the use of a Building Communications Interface (BCI).
A twisted pair network topology (FT-10) may be a maximum length of 6000 feet per network segment with no T-
taps, allowing communications between 64 nodes in each segment. In addition FT-10 allows dedicated runs of
8000 feet point-to-point or multiple T-taps within 1500 feet of any other node on the segment. Fiber optic cable is
another option and can be configured in either a bus or ring topology. The network has a maximum system
capacity of 200 nodes. The network is supervised for shorts, opens, and node failures, as dictated in Style 4, 6 and
7 wiring.
The network power is 24 VDC nominal and receives operating power from a power limited, filtered source listed for
use with fire protective signaling units.