User Manual
Table Of Contents
- _
- Foreword
- Introduction
- Section One: Simplex 4010 NION Hardware
- 1.1: General Description
- 1.2: Hardware Description
- Figure 1-1: NION-NPB Layout
- 1.3: SMX Network Connection
- Figure 1-2: SIMPLEX 4010 NION TB5 Power Connection
- 1.4: SMX Network Transceivers
- Figure 1-3: FTXC-PCA and FTXC-PCB Network Transceivers
- Figure 1-3a: FTXC-PCA Transceiver Wiring
- Figure 1-4: S7FTXC-PCA Style 7 Transceiver
- Figure 1-5: Sample Style-7 Networks
- Figure 1-6: FOXC-PCA and DFXC-PCA Fiber Optic Network Transceivers
- Section Two: Simplex 4010 NION Installation and Configuration
- 2.1: Simplex 4010 NION Connection
- Figure 2-1: Simplex 4010 NION Architecture
- Figure 2-2: Simplex 4010 NION to Simplex 4010-9811 Serial Connections
- 2.2: Simplex 4010 NION Enclosure and Mounting
- Figure 2-4: NISCAB-1 Enclosure Mounting Hole Layout
- 2.3 Event Reporting and Acknowledgement
- Figure 2-5: Installing the NION in a NISCAB-1
- Section Three: Simplex 4010 NION Explorer
- 3.1 Simplex Explorer Overview
- 3.2 Simplex 4010 Explorer Operation
- 3.2.1 Registering and Opening the Simplex Explorer
- 3.2.2 The Simplex 4010 Explorer Main Form
- 3.2.3 Configuring the NION through Simplex 4010 Explorer
- Figure 3-2: NION-Simplex 4010 Configuration Menu
- Figure 3-1: Simplex 4010 Explorer
- Figure 3-4: Duplicate Device Labels
- Figure 3-3: Learn Panel Devices Session
- Figure 3-5: Data Capture Mode
- Figure 3-6: NION Configuration Options
7
Simplex 4010 NION Installation/Operation Manual Version 2 Document 51998 Rev. A1 03/26/03
Foreword
The contents of this manual are important and must be kept in close proximity of the UniNet™ Facilities Monitoring
System. If building ownership is changed, this manual and all other testing and maintenance information must also
be passed to the current owner of the facility. A copy of this manual was shipped with the equipment and is also
available from the manufacturer.
NFPA Standards
• National Fire Protection Association Standards 72 (NFPA 72).
• National Electric Code (NFPA 70).
• Life Safety Code (NFPA 101).
Underwriters Laboratories U.S. Documents
• UL-864 Control Units for Fire Protective Signaling Systems (Ancillary monitoring only).
Other
• Requirements of the Local Authority Having Jurisdiction (LAHJ).
WARNING:WARNING:
WARNING:WARNING:
WARNING: Improper installation, maintenance, and lack of routine testing could result in system malfunction.
Introduction
The NION-Simplex 4010 is a plug-in component of the UniNet™ 2000 Workstation. It allows a workstation to
view events and other data originating from a Simplex 4010 panel.
UniNet™ consists of graphical workstations monitoring and controlling, local or remote twisted pair or fiber optic
networks. Remote network monitoring is achieved through the use of a Building Communications Interface (BCI).
A twisted pair network topology (FT-10) may be a maximum length of 6000 feet per network segment with no T-
taps, allowing communications between 64 nodes in each segment. In addition FT-10 allows dedicated runs of
8000 feet point-to-point or multiple T-taps within 1500 feet of any other node on the segment. Fiber optic cable is
another option and can be configured in either a bus or ring topology. The network has a maximum system
capacity of 200 nodes. The network is supervised for shorts, opens, and node failures, as dictated in Style 4, 6 and
7 wiring.
The network power is 24 VDC nominal and receives operating power from a power limited, filtered source listed for
use with fire protective signaling units.
Related Documentation
Network Installation Manual 51539 UniLogic 51547
Workstation 51540 AM2020/AFP1010 Instruction Manual 52020
System Utilities 51592 UniTour 51550
BCI ver. 3-3 51543 IRM/IM 51591
Local Area Server 51544 UniNet Online 51994
Technical Manuals Online! - http://www.tech-man.com