User Manual
Table Of Contents
- _
- Foreword
- Introduction
- Section One: Simplex 4010 NION Hardware
- 1.1: General Description
- 1.2: Hardware Description
- Figure 1-1: NION-NPB Layout
- 1.3: SMX Network Connection
- Figure 1-2: SIMPLEX 4010 NION TB5 Power Connection
- 1.4: SMX Network Transceivers
- Figure 1-3: FTXC-PCA and FTXC-PCB Network Transceivers
- Figure 1-3a: FTXC-PCA Transceiver Wiring
- Figure 1-4: S7FTXC-PCA Style 7 Transceiver
- Figure 1-5: Sample Style-7 Networks
- Figure 1-6: FOXC-PCA and DFXC-PCA Fiber Optic Network Transceivers
- Section Two: Simplex 4010 NION Installation and Configuration
- 2.1: Simplex 4010 NION Connection
- Figure 2-1: Simplex 4010 NION Architecture
- Figure 2-2: Simplex 4010 NION to Simplex 4010-9811 Serial Connections
- 2.2: Simplex 4010 NION Enclosure and Mounting
- Figure 2-4: NISCAB-1 Enclosure Mounting Hole Layout
- 2.3 Event Reporting and Acknowledgement
- Figure 2-5: Installing the NION in a NISCAB-1
- Section Three: Simplex 4010 NION Explorer
- 3.1 Simplex Explorer Overview
- 3.2 Simplex 4010 Explorer Operation
- 3.2.1 Registering and Opening the Simplex Explorer
- 3.2.2 The Simplex 4010 Explorer Main Form
- 3.2.3 Configuring the NION through Simplex 4010 Explorer
- Figure 3-2: NION-Simplex 4010 Configuration Menu
- Figure 3-1: Simplex 4010 Explorer
- Figure 3-4: Duplicate Device Labels
- Figure 3-3: Learn Panel Devices Session
- Figure 3-5: Data Capture Mode
- Figure 3-6: NION Configuration Options
21
Simplex 4010 NION Installation/Operation Manual Version 2 Document 51998 Rev. A1 03/26/03
NION-Simplex 4010 Configuration Menu
LL
LL
L
earn Pearn P
earn Pearn P
earn P
anel Devicesanel Devices
anel Devicesanel Devices
anel Devices - This selection allows the NION to learn, or self program, all the devices associated with
the Simplex 4010 panel it is connected to. This selection will start a panel learn session and the data display area
will show a progress bar and the number of device types the NION has detected on the panel. When the panel
learn session is complete, a message will appear. Click OK and click the Close button. The Simplex 4010
NION is now configured with the Simplex 4010 devices.
Figure 3-3: Learn Panel Devices Session
NOTE: The Learn Panel
Devices session is a lengthy
process. Please allow several
minutes for this operation.
NOTE: The NION will not
function properly unless a
Panel Learn session is
executed. If devices or
labels are added or
changed, a Panel Learn
must be performed again.
Figure 3-4: Duplicate Device Labels
The Simplex 4010 devices must not have any duplicate device labels. If duplicate device labels are found during a
panel learn session, a message will appear on the Simplex Explorer screen. If any duplicates are found, the
Simplex NION Explorer creates a log file and saves it in the C:\UniNet\PlugIns\Data\ file folder, with a file name
of Simplex4010_node_XXX_duplicates.log (where XXX denotes the NION number). This file will list all dupli-
cate labels and their addresses. All point labels must be unique for proper functionality.
Enter Data Capture ModeEnter Data Capture Mode
Enter Data Capture ModeEnter Data Capture Mode
Enter Data Capture Mode - This selection changes the data display into a display of panel messages for
troubleshooting purposes. Simplex Explorer gives the option to save this information as a log file when Enter Data
Capture Mode is first selected. This file is written as follows:
C:\UniNet\PlugIns\Data\Simplex 4010_node_XXX_data_capture.log