User Manual
Table Of Contents
- _
- Foreword
- Introduction
- Section One: Simplex 4010 NION Hardware
- 1.1: General Description
- 1.2: Hardware Description
- Figure 1-1: NION-NPB Layout
- 1.3: SMX Network Connection
- Figure 1-2: SIMPLEX 4010 NION TB5 Power Connection
- 1.4: SMX Network Transceivers
- Figure 1-3: FTXC-PCA and FTXC-PCB Network Transceivers
- Figure 1-3a: FTXC-PCA Transceiver Wiring
- Figure 1-4: S7FTXC-PCA Style 7 Transceiver
- Figure 1-5: Sample Style-7 Networks
- Figure 1-6: FOXC-PCA and DFXC-PCA Fiber Optic Network Transceivers
- Section Two: Simplex 4010 NION Installation and Configuration
- 2.1: Simplex 4010 NION Connection
- Figure 2-1: Simplex 4010 NION Architecture
- Figure 2-2: Simplex 4010 NION to Simplex 4010-9811 Serial Connections
- 2.2: Simplex 4010 NION Enclosure and Mounting
- Figure 2-4: NISCAB-1 Enclosure Mounting Hole Layout
- 2.3 Event Reporting and Acknowledgement
- Figure 2-5: Installing the NION in a NISCAB-1
- Section Three: Simplex 4010 NION Explorer
- 3.1 Simplex Explorer Overview
- 3.2 Simplex 4010 Explorer Operation
- 3.2.1 Registering and Opening the Simplex Explorer
- 3.2.2 The Simplex 4010 Explorer Main Form
- 3.2.3 Configuring the NION through Simplex 4010 Explorer
- Figure 3-2: NION-Simplex 4010 Configuration Menu
- Figure 3-1: Simplex 4010 Explorer
- Figure 3-4: Duplicate Device Labels
- Figure 3-3: Learn Panel Devices Session
- Figure 3-5: Data Capture Mode
- Figure 3-6: NION Configuration Options
17
Simplex 4010 NION Installation/Operation Manual Version 2 Document 51998 Rev. A1 03/26/03
2.2: Simplex 4010 NION Enclosure and Mounting
For NION mounting applications where power is supplied by the monitored equipment or an external source, the
NISCAB-1 should be used. This enclosure is provided with door and key lock.
Mounting the enclosure to its wall position
1) Use the provided key to unlock the enclosure cover.
2) Remove the enclosure cover.
3) Mount the enclosure to the wall. Refer to the enclosure mounting hole layout below.
Figure 2-4: NISCAB-1 Enclosure Mounting Hole Layout
Power Requirements and Connection
The Simplex 4010 NION requires
24VDC @ 250mA nominal in
accordance with local code require-
ments. It can be powered by any
power limited, regulated source that
is UL listed for use with fire protective
signaling units.
+24VDC+24VDC
+24VDC+24VDC
+24VDC
GNDGND
GNDGND
GND
Simplex 4010 NIONSimplex 4010 NION
Simplex 4010 NIONSimplex 4010 NION
Simplex 4010 NION
Figure 2-3: Simplex 4010 NION Power Connection