1.11 EVENT REPORTING FORMAT
All Event reporting from the AFP-300/400 NION appears at the Workstation in the following format:
NNNSSSXXXXXXXX
Where NNN is the network node number for the AFP-300/400 NION.
Where SSS is the node number programmed in the AFP-300/400 panel.
Where XXXXXXXX is an 8 digit device ID.
The 8 digit ID will conform to one of the following formats, depending on the nature of the device.
87654321
Detectors: LllDddd Lll = loop, Dddd = detector
Modules: LllMmmm Lll = loop, Mmmm = module
Annunciators: ANNUNaa aa = annunciator
Annunciator Points: AaaPppp aa = annunciator, ppp = point
Bell Circuits: BC cc cc = circuit
Panel Circuits: PC cc-p cc = circuit, p = point
Zones: ZONEzzz zzz = zone
Panel: Panel
Ground: GROUND
Battery: BATTERY
AC Power: ACPOWER
Audibles: Audible
Example 1:
Echelon Node 001, AFP-300/400 Panel programmed as node 007, Loop 02, Detector 003 reports with the
following device ID:
001007 L02D003
Example 2:
Echelon Node 007, AFP-300/400 Panel programmed as node 003, Bell Circuit 01 reports with the following
device ID:
007003 BC 01
Example 3:
Echelon Node 003, AFP-300/400 Panel programmed as node 001, Zone 004 reports with the following device
ID:
003001 ZONE004