Instruction Manual

11
Document 51996 AFP-300/400 NION Installation Rev. A1 03/04/03
1.2 AFP-300/400 NION Connectors
Power Connector (TB5) - +24VDC input power connector.
TB6 - Relay output; both Normally Open/Normally Closed are available (contact rating: 2A 30VDC). All rated
loads are resistive.
TB1 - Standard terminal block style port for EIA-232 connection to serial channel A.
Echelon Network Transceiver Connector(J1) - Pin connection header for SMX Transceiver.
Reset Pin (SW1) - Resets the NION and restarts the software.
Bind Pin (SW2) - Sends a message to the Local Area Server requesting to be added to the network.
Battery Terminal (BT1) - 3V Lithium battery terminal (replacement battery P/N - LITHBATT-3V).
Network Communication PLCC (U24) - The flash module that specifies the network transceiver.
Application PLCC (U6) - The flash module that contains the application software.
Environmental Requirements
The AFP-300/400 NION can be installed in the following environmental conditions:
Temperature range of 0ºC to 49ºC (32°F - 120°F).
93% humidity non-condensing at 30ºC (86°F).
1.4 Cabinet Mounting Information
The AFP-300/400 NION board can be installed in any NOTIFIER® CAB-3 or CAB-4 series cabinet, a
NOTIFIER® NISCAB-1, or an ABS-4DB Annunciator Backbox (surface mount). The NISCAB-1 allows the installa-
tion of one NION.
The AFP-300/400 NION board is designed to be installed on a wall within 20 feet in conduit of the control panel
in the same room. The type of hardware used is at the discretion of the installer, but it must be in accordance with
local code requirements.
CAB-3/CAB-4 Series Installation
The CHS-4L or CHS-M2 chassis gets mounted into a CAB-3 or CAB-4 series cabinet.
Figure 1-3: CAB-A3/4 Enclosure
1.3 Installation Description
Required Components
NION-SPB
SMX Transceiver (FTXC, S7FTXC, FOXC, or DFXC)
Software kit for AFP-300/400 NION interface
Enclosure (CAB-3 or CAB-4 series cabinet, NISCAB-1, or ABS-4DB)
The following paragraphs describe all required and optional components used to assemble a functional AFP-300/
400 NION. All of the items described must be ordered separately.