Instruction Manual
DN-6710:A • 10/17/06 — Page 1 of 2
SpectrAlert®
SP200, SP201, SP300, SP301
Dual-Voltage Evacuation Speakers
Audio/Visual Devices
DN-6710:A • J-111
Ceiling/Wall-Mount
Application
Wall-Mount
Application
6710cov.jpg
General
System Sensor® SP2 and SP3 Series speakers combine per-
formance, functionality, and flexibility in the latest line of dual-
voltage evacuation speakers.
Performance. With its low total harmonic distortion, the Spec-
trAlert SP2 Series offers fidelity-quality sound output. This per-
formance provides greater assurances that the SP2’s output
more closely matches the source signal. This fidelity sound
quality is achieved at any of the SP2’s four field-selectable
power taps: 1/4, 1/2, 1, and 2 watts. The SpectrAlert SP3
Series offers greater sound output at every tap setting for
applications with high ambient noise levels.
Functionality. Installation ease and functionality are achieved
via the speaker’s compact design, which allows flush mounting
to a 4.0" x 4.0" x 2.125" (10.16 x 10.16 x 5.398 cm) backbox,
without the need for an extension ring.
Flexibility. The SP2 and SP3 Series speakers are designed
for a variety of application requirements. Offered with round
and square grilles, they can be ceiling or wall mounted. White
and red grille color options are also available to meet specific
aesthetic requirements.
Features
Fidelity sound quality (SP2).
Enhanced SPL (SP3).
25.0 and 70.7 V
RMS dual-voltage settings.
Four field-selectable power taps.
No extension ring required.
Low-profile design.
Ceiling- and wall-mount applications.
Grilles available in white and red.
Color-matched mounting screws.
Engineering Specifications
Speaker shall be a System Sensor Model ________ dual-volt-
age transformer speaker capable of operating at 25.0 or 70.7
nominal V
RMS. Speaker shall be listed to Underwriters Labora-
tories’ Standard 1480 for fire protective signaling systems.
Speaker shall have a frequency range of 400 to 4000 Hz and
shall have an operating temperature between 32°F and 120°F
(0°C and 49°C). Speaker shall have power taps that are
selected by shunts.
Operating Specifications
MECHANICAL
Input terminals: 12 to 18 AWG (3.31 to 0.821 mm²).
Speaker size: 4 inches (101 mm).
Grille size:
round 6.875 inches (107 mm); square 5 inches
(127 mm).
ELECTRICAL
Voltage Input: 25.0 volts or 70.7 volts nominal.
Frequency range: 400 to 4000 Hz.
NOTE: The SP200 and
SP300 Series are UL Listed from 400 to 4000 Hz. The SP200
Series will provide a flat (±10 dB) output from 100 to 15,000
Hz. The SP300 Series will provide a flat (±10 dB) output from
500 to 13,000 Hz.
Operating temperature range: 32°F to 120°F (0°C to 49°C).
Power: 1/4, 1/2, 1 and 2 watts.
Sound Output
Agency Listings and Approvals
The listings and approvals below apply to SpectrAlert Dual-
Voltage Evacuation Speakers. In some cases, certain modules
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
• UL Listed: file S4048.
• ULC Listed: file CS548 (SP200W/R[A], SP200W/R[A]).
• MEA approved:
– file 461-05-E (SP300W, SP301R, SP301W).
– file 353-98-E (SP200W/R[A], SP201W/R[A]).
– file 139-05-E (SP201K, SP2R1224MCK).
• CSFM approved: 7320-1653:183
UL Reverberant (dBA @ 10 ft./3.048 m)
2 W 1 W 1/2 W 1/4 W
SP284817875
SP389868480
firealarmresources.com