Owner's Manual

DN-60640:A2 • 12/03/2010 — Page 1 of 4
Spartan-25® (NSP-25C)
Addressable FACP
With Built-in Communicator
Addressable Fire Alarm Control Panels
Canadian DN-60640:A2
spartan_sm.JPG
General
The NOTIFIER Spartan-25 (NSP-25C) is a 25 point address-
able Fire Alarm Control Panel (FACP) with built-in Digital
Alarm Communicator Transmitter (DACT). This control panel
supports up to 25 addressable devices in any combination of
detectors and modules and then reports these devices into
one of 5 available zones.
With simple programming, operation on standard wire, and
features such as drift compensation and maintenance alert,
the Spartan-25 is a preferred alternative to conventional con-
trol panels in both new and retrofit applications.
The JumpStart® (or auto-learn) feature and easy-to-set code-
wheel addressing of Honeywell Fire Systems detectors and
modules enable the system to be quickly configured for fire
protection without a programming utility. The default program-
ming can be easily modified on a PC using the panel’s embed-
ded web server.
The integral DACT transmits system status (alarms, troubles,
supervisories, etc.) for up to 5 zones to a remote monitoring
location via the public switched telephone network. Reporting
formats are contact ID, SIA 8 or SIA 20.
Features
ULC listed and ETL certified to ULC Standard S527 and
S559
JumpStart® auto-learn feature reduces installation time
and makes programming easy.
Built-in digital communicator.
Two programmable Style Y (Class B) notification appliance
circuits (NACs).
Selectable strobe synchronization for System Sensor®,
Gentex®, Wheelock® or AMSECO devices.
Two programmable Form-C relays and one Form-C trouble
relay.
Drift compensation.
Alarm verification per zone of detectors.
Walk-test.
Honeywell Fire Systems detectors and modules are code-
wheel addressed for faster installation time.
Maintenance alert region.
Uses standard wire (unshielded or twisted pair).
Central Station reporting up to five zones.
On Board Annunciator.
Custom programming performed through the control
panel’s built-in browser; no programming software is
required.
DCL Communication
Single addressable DCL loop which meets ULC DCLB
requirements.
25 addressable device capacity (any combination of
addressable detectors and modules).
Compatible with Honeywell Fire Systems detectors and
modules.
Notification Appliance Circuits (NACS)
Two independently programmable output circuits. Circuits
can be configured for the following outputs:
Style Y (Class B).
Door Holder Service (cannot be used for notification
appliances).
Aux Power Source (cannot be used for notification appli-
ances).
Silence Inhibit and Auto-silence timer options.
Continuous or Temporal code.
Selectable strobe synchronization per NAC.
Up to 2.0 A total output power, 1.0 A for auxiliary power and
door holder. Each circuit can source up to the total system
current 2.0 A.
Programming and Software
Auto-learn “JumpStart®” feature for easy programming
reduces installation time.
Custom programming can be performed through control
panel’s built-in browser. (Requires PC with MS Internet
Explorer or Mozilla Firefox and standard Cat5e Ethernet
cable)
5 programmable zones (combination of alarm / supervisory)
firealarmresources.com