Instructions

DN-60609:B1 • 08/19/2010 — Page 1 of 4
Spartan-25® (NSP-25/E)
Addressable FACP
With Built-in Communicator
Addressable Fire Alarm Control Panels
DN-60609:B1
spartan_sm.JPG
General
The NOTIFIER Spartan-25 (NSP-25/NSP-25E) is a 25 point
addressable Fire Alarm Control Panel (FACP) with built-in Dig-
ital Alarm Communicator Transmitter (DACT). This control
panel supports up to 25 addressable devices in any combina-
tion of detectors and modules. With simple programming,
operation on standard wire, and features such as drift compen-
sation and maintenance alert, the Spartan-25 is a preferred
alternative to conventional control panels in both new and ret-
rofit applications.
The JumpStart® (or auto-learn) feature and easy-to-set code-
wheel addressing of Honeywell Fire Systems detectors and
modules enable the system to be configured for fire protection
without a programming utility. The default programming can be
modified using the panels embedded web server.
The integral DACT transmits system status (alarms, troubles,
supervisories, etc.) to a remote monitoring location via the
public switched telephone network. Reporting formats are con-
tact ID, SIA 8 or SIA 20.
NOTE: Unless otherwise specified, the term Spartan-25 is
used in this data sheet to refer to the Spartan-25 and the Spar-
tan-25E. For details on the Canadian version, see DN-60640.
Features
ETL listed to ANSI/UL 864 9th Edition Standard
Listed to UL Standard 864, Ninth edition.
JumpStart® auto-learn feature reduces installation time
and makes programming easy.
Built-in digital communicator.
Two programmable Style Y (Class B) notification appliance
circuits (NACs).
Selectable strobe synchronization for System Sensor®,
Gentex®, Wheelock® or AMSECO devices.
Two programmable Form-C relays and one Form-C trouble
relay.
Automatic detector sensitivity testing (NFPA 72 compliant).
Drift compensation.
Alarm verification per zone of detectors.
Walk-test.
Maintenance alert region.
Uses standard wire (unshielded or twisted pair).
Custom programming performed through the control
panel’s built-in browser; no programming software is
required.
Fire Zones
SLC Communication
Single addressable SLC loop which meets NFPA Style 4
(Class B) requirements.
25 addressable device capacity (any combination of
addressable detectors and modules).
Compatible with Honeywell Fire Systems detectors and
modules.
Notification Appliance Circuits (NACS)
Two independently programmable output circuits. Circuits
can be configured for the following outputs:
Style Y (Class B).
Door Holder Service (cannot be used for notification
appliances).
Aux Power Source (cannot be used for notification appli-
ances).
Silence Inhibit and Auto-silence timer options.
Continuous or Temporal code.
Selectable strobe synchronization per NAC.
Up to 2.0 A total output power, 1.0 A for auxiliary power and
door holder. Each circuit can source up to the total system
current 2.0 A.
Programming and Software
Auto-learn “JumpStart®” feature for easy programming
reduces installation time.
Custom programming can be performed through control
panel’s built-in browser.
firealarmresources.com