Instructions
DN-60609:B1 • 08/19/2010 — Page 1 of 4
Spartan-25® (NSP-25/E)
Addressable FACP
With Built-in Communicator
Addressable Fire Alarm Control Panels
DN-60609:B1
spartan_sm.JPG
General
The NOTIFIER Spartan-25 (NSP-25/NSP-25E) is a 25 point
addressable Fire Alarm Control Panel (FACP) with built-in Dig-
ital Alarm Communicator Transmitter (DACT). This control
panel supports up to 25 addressable devices in any combina-
tion of detectors and modules. With simple programming,
operation on standard wire, and features such as drift compen-
sation and maintenance alert, the Spartan-25 is a preferred
alternative to conventional control panels in both new and ret-
rofit applications.
The JumpStart® (or auto-learn) feature and easy-to-set code-
wheel addressing of Honeywell Fire Systems detectors and
modules enable the system to be configured for fire protection
without a programming utility. The default programming can be
modified using the panels embedded web server.
The integral DACT transmits system status (alarms, troubles,
supervisories, etc.) to a remote monitoring location via the
public switched telephone network. Reporting formats are con-
tact ID, SIA 8 or SIA 20.
NOTE: Unless otherwise specified, the term Spartan-25 is
used in this data sheet to refer to the Spartan-25 and the Spar-
tan-25E. For details on the Canadian version, see DN-60640.
Features
• ETL listed to ANSI/UL 864 9th Edition Standard
• Listed to UL Standard 864, Ninth edition.
• JumpStart® auto-learn feature reduces installation time
and makes programming easy.
• Built-in digital communicator.
• Two programmable Style Y (Class B) notification appliance
circuits (NACs).
• Selectable strobe synchronization for System Sensor®,
Gentex®, Wheelock® or AMSECO devices.
• Two programmable Form-C relays and one Form-C trouble
relay.
• Automatic detector sensitivity testing (NFPA 72 compliant).
• Drift compensation.
• Alarm verification per zone of detectors.
• Walk-test.
• Maintenance alert region.
• Uses standard wire (unshielded or twisted pair).
• Custom programming performed through the control
panel’s built-in browser; no programming software is
required.
• Fire Zones
SLC Communication
• Single addressable SLC loop which meets NFPA Style 4
(Class B) requirements.
• 25 addressable device capacity (any combination of
addressable detectors and modules).
• Compatible with Honeywell Fire Systems detectors and
modules.
Notification Appliance Circuits (NACS)
• Two independently programmable output circuits. Circuits
can be configured for the following outputs:
– Style Y (Class B).
– Door Holder Service (cannot be used for notification
appliances).
– Aux Power Source (cannot be used for notification appli-
ances).
• Silence Inhibit and Auto-silence timer options.
• Continuous or Temporal code.
• Selectable strobe synchronization per NAC.
• Up to 2.0 A total output power, 1.0 A for auxiliary power and
door holder. Each circuit can source up to the total system
current 2.0 A.
Programming and Software
• Auto-learn “JumpStart®” feature for easy programming
reduces installation time.
• Custom programming can be performed through control
panel’s built-in browser.
firealarmresources.com