Instruction Manual

DN-60703:A1 • 9/19/2011 — Page 1 of 4
NSP-25(E) Rev 2
Spartan-25® Addressable FACP
With Built-in Communicator
Intelligent Fire Alarm Control Panels
DN-60703:A1
spartan_sm.JPG
General
The NOTIFIER Spartan-25 (NSP-25/NSP-25E) is a 25 point
addressable Fire Alarm Control Panel (FACP) with built-in Dig-
ital Alarm Communicator Transmitter (DACT). This control
panel supports up to 25 addressable devices in any combina-
tion of detectors and modules. With simple programming,
operation on standard wire, and features such as drift compen-
sation and maintenance alert, the Spartan-25 is a preferred
alternative to conventional control panels in both new and ret-
rofit applications.
The JumpStart® (or auto-learn) feature and easy-to-set code-
wheel addressing of Honeywell Fire Systems (HFS) or equiva-
lent Notifier detectors and modules enable the system to be
configured for fire protection without a programming utility. The
default programming can be modified using the panels embed-
ded web server.
The integral DACT transmits system status (alarms, troubles,
supervisories, etc.) to a remote monitoring location via the
public switched telephone network. Reporting formats are con-
tact ID, SIA 8 or SIA 20.
NOTE: Unless otherwise specified, the term Spartan-25 is
used in this data sheet to refer to the Spartan-25 and the Spar-
tan-25E. For details on the Canadian version, see DN-60705.
Features
SBUS supports two ANN-80 Remote Annunciators
JumpStart® auto-learn feature reduces installation time
and makes programming easy.
Built-in digital communicator.
IP communicator compatible
Two programmable Style Y (Class B) notification appliance
circuits (NACs).
Selectable strobe synchronization for System Sensor®,
Gentex®, Wheelock® or AMSECO devices.
Two programmable Form-C relays and one Form-C trouble
relay.
Automatic detector sensitivity testing (NFPA 72 compliant).
Point status eliminates calibrated smoke test requirements
for NFPA 72.
Drift compensation.
Alarm verification per zone of detectors.
Walk-test.
Detectors and modules are code-wheel addressed for
faster installation time.
Maintenance alert region.
Uses standard wire (unshielded or twisted pair).
Central Station reporting up to five zones.
Custom programming performed through the control
panel’s built-in browser; no programming software is
required.
SLC Communication
Single addressable SLC loop which meets NFPA Style 4
(Class B) requirements.
25 addressable device capacity (any combination of
addressable detectors and modules).
Compatible with Honeywell Fire Systems (HFS) or equiva-
lent Notifier detectors and modules.
Notification Appliance Circuits (NACS)
Two independently programmable output circuits. Circuits
can be configured for the following outputs:
Style Y (Class B).
Door Holder Service (cannot be used for notification
appliances).
Aux Power Source (cannot be used for notification appli-
ances).
Silence Inhibit and Auto-silence timer options.
Continuous or Temporal code.
Selectable strobe synchronization per NAC.
Up to 2.0 A total output power, 1.0 A for auxiliary power and
door holder. Each circuit can source up to the total system
current 2.0 A.
Programming and Software
Auto-learn JumpStart® feature for easy programming
reduces installation time.
Custom programming can be performed through control
panel’s built-in browser.