PROGRAMMING AND COMMISSIONING
Conguring the Output Module Mode
The output module is supplied congured as a Supervised Output
Module (factory default setting). To change the output to relay
mode (Form C - volt-free changeover contacts) requires a separate
programming operation using the Device Direct Command in AgileIQ
(See Radio Programming and Commissioning Manual - ref. D200-
306-00 for details.)
Starting with an un-commissioned module:
1) Remove it from the back box.
2) Ensure that the address is set to 00 (default setting).
3) Insert the batteries.
4) Select the Device Direct Command tab in AgileIQ.
5) Double click on the screen to reveal the list of options and follow
the instructions to congure the output module mode.
Note: Remove the batteries from the device afterwards if the system
commissioning operation is not about to be done.
It is recommended that the output module conguration is noted for
future reference on the module label after commissioning:
OUTPUT MODULE: Supervised ¨ Relay ¨
Commissioning
1) Remove the module from the back box.
2) Ensure that the correct address has been set.
3) Insert the batteries.
4) Ret the module and replace the back box front cover.
To load network parameters into the RF module, it is necessary to link
the RF gateway and the RF module in a conguration operation using
the AgileIQ software tool. At commissioning time, with the RF network
devices powered on, the RF gateway will connect and program them
with network information as necessary.
The RF module then synchronises with its other associated devices
as the RF mesh network is created by the Gateway. (For further
information, see the Radio Programming and Commissioning
Manual - ref. D200-306-00.)
NOTE: Do not run more than one USB interface at a time to
commission devices in an area.
WIRING DIAGRAMS
Figure 7: Input / Output Module Relay Mode
Figure 6: Output Module Supervised
Patents Pending
EU Declaration of Conformity
Hereby, Notier by Honeywell declares that the radio equipment type
NRX-M711 is in compliance with directive 2014/53/EU
The full text of the EU DoC can be requested from:
HSFREDDoC@honeywell.com
EN54-25: 2008 / AC: 2010 / AC: 2012
Components Using Radio Links
EN54-18: 2005 / AC: 2007 Input/Output Devices
for use in re detection and re alarm systems for buildings
0333 19
DOP-IRF026
Notier Fire Systems by Honeywell
Pittway Tecnologica S.r.l. Via Caboto 19/3
34147 TRIESTE, Italy