SPECIFICATIONS
Sensitivity:
• UL Applications: 0.5% to 4.0% per foot obscuration.
• ULC Applications: 0.5% to 3.5% per foot obscuration
Size: 2.0" (5.3 cm) high; base determines diameter
– B300-6: 6.1" (15.6 cm) diameter
– B501: 4" (10.2 cm) diameter
For a complete list of detector bases see DN-60981
Shipping weight: 3.4 oz. (95 g)
Operating temperature range:
• NP-200: 32°F to 122°F (0°C to 50°C)
• NP-200T Series: 32°F to 100°F(0°C to 38°C)
• NP-200R Series installed in a DNR/DNRW, -4°F to 158°F (-20°C
to 70°C)
UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.),
suitable for installation in ducts
Relative humidity: 10% – 93% non-condensing
Thermal ratings: fixed-temperature set point 135
°F (57°C), rate-of-
rise detection 15°F (8.3°C) per minute, high temperature heat 190°F
(88°C)
ELECTRICAL SPECIFICATIONS
Voltage range: 15 - 32 volts DC peak
Standby current (max. avg.): 200µA @ 24 VDC (one communica-
tion every 5 seconds with LED enabled)
Max current: 4.5 mA @ 24 VDC (“ON”)
DETECTOR SPACING AND APPLICATIONS
NOTIFIER recommends spacing detectors in compliance with NFPA
72. In low airflow applications with smooth ceiling, space detectors
30 feet (9.1m). For specific information regarding detector spacing,
placement, and special applications refer to NFPA 72. A System
Smoke Detector Application Guide, document A05-1003, is avail-
able at www.systemsensor.com.
Listings and Approvals
Listings and approvals below apply to the NP-200 Series detectors.
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for
latest listing status.
• UL/ULC Listing: S1115
• FM Approved