Owner's Manual
DN-7070:P • 3/8/17 — Page 7 of 8
on a half-chassis and one NFS2-3030 or NCA-2 mounted on a
half-chassis. The right side houses a microphone/handset
well. The CA-2 assembly includes CMIC-1 microphone. ADDR
Series doors with two-tier visibility are available for use with
the CA-2 configuration: ADDR-B4, ADDR-C4, ADDR-D4
(below).
ADDR-B4: Two-tier-sized door designed for use with the CA-2
chassis configuration. ADDR Series doors are similar to CAB-
4 Series “DR” doors, but a clear window space exposes the
top two tiers of the CAB-4 enclosure. Use an SBB-B4 backbox
with the ADDR-B4. See DN-7045, DN-6857.
ADDR-C4: Three-tier-sized door designed for use with the CA-
2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-C4
backbox with the ADDR-C4. See DN-7045, DN-6857.
ADDR-D4: Four-tier-sized door designed for use with the CA-2
chassis configuration. ADDR Series doors are similar to CAB-
4 Series “DR” doors, but a clear window space exposes the
top two tiers of the CAB-4 enclosure. Use an SBB-D4 backbox
with the ADDR-D4. See DN-7045, DN-6857.
DPA-1: Dress panel, used with the CA-1 chassis when config-
ured with a
DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
DPA-2: Dress Panel used with the CA-2 chassis assembly.
DPA-1A4: Dress panel, used with the CA-1 chassis when the
CMIC-1 is not used. Provides mounting options on right two
bays for two ACS annunciators, or for blank plates. See DN-
7045.
ADP-4B: Annunciator dress plate. Mounts in rows 2, 3 or 4 of
a CAB-4 series enclosure. Used with ACS series annuncia-
tors.
BMP-1: Blank module for unused module positions.
DP-1B: Blank dress panel. Provides dead-front panel for
unused tiers; covers DAA2/DAX series or AA-series amplifier.
BP2-4: Battery plate, required.
CHS-4L: Low-profile four-position Chassis. Mounts two AA-30
amplifiers.
CHS-4N: Chassis for mounting up to four APS-6Rs.
CHS-6: Chassis used with the XP6 and XP10 Multi-Modules.
Mounts up to six modules in any CAB-4 series row.
NFS-LBB: Battery Box. The NFS-LBB is used to mount up to
two 55 AH batteries. Dimensions: Box: 24" (610 mm) wide x
14" (356 mm) high x 7.75" (197 mm) deep. Door: 24.125" (613
mm) wide x 14.25" (362 mm) high; door adds 0.0625" (approx.
1.6 mm) to depth.
BACKBOXES
NOTE: “C” suffix indicates ULC-Listed model.
BB-100: Backbox for batteries and power supplies. The BB-
100 is used to mount up to two 100 AH batteries and power
supply, if needed. 30" (76.20 cm) wide x 25" (63.50 cm) high x
7.5" (19.05 cm) deep; depth includes door.
BB-200: Backbox for batteries and power supplies. Holds up
to four 100 AH batteries (200 AH capacity) and power supply.
30" (76.20 cm) wide x 36" (91.44 cm) high x 7.5" (19.05 cm)
deep; depth includes door.
BB-UZC: Backbox for housing the UZC-256 for applications
where the UZC will not fit in panel enclosure. Black; for red,
order BB-UZC-R. See DN-3404.
ABF-1B(C) Annunciator Flush Box
ABF-1DB(C) Annunciator Flush Box with Door.
UL/ULC Listed.
ABF-2B Annunciator Flush Box
ABF-2DB(C) Annunciator Flush Box with Door
ABF-4B Annunciator Flush Box
ABS-1TB(C) Annunciator Surface Box
ABS-1B(C) Annunciator Surface Box
ABS-2B Annunciator Surface Box
ABS-2D(C) Annunciator Surface Box
ABS-4D(C) Annunciator Surface Box
SEISKIT-CAB: Seismic mounting kit. Required for seismic-
certified applications with NFS2-3030 and other equipment
mounted in CAB-4 Series Enclosures. Includes battery bracket
for
two 26 AH batteries.
SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery
bracket for two 55 AH batteries.
OTHER OPTIONS
411: Slave digital alarm communicator. See DN-6619.
411UDAC: Digital alarm communicator. See DN-6746.
IPDACT-2, IPDACT Internet Monitoring Module: Connects
to primary and secondary DACT telephone output ports for
internet communications over customer-provided Ethernet
connection. Requires compatible Teldat VisorALARM Central
Station Receiver. Can use DHCP or static IP. See DN-60408.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For
mounting an IPDACT-2/2UD onto the panel chassis or CHS-4
series chassis. Use IPENC for external mounting applications.
IPSPLT: Y-adapter option allow connection of both panel dialer
outputs to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT
mounting bracket; Red; for black, order IPENC-B.
IPGSM-4G: Internet and Digital Cellular Fire Alarm Communica-
tor. Provides selectable configurable paths: cellular only, IP only,
or IP primary with cellular backup. Connects to the primary and
secondary ports of a DACT. For Canadian applications order
IPGSM-4GC. See DH-60769.
NOTE: For other options including compatibility with retrofit equip-
ment, refer to the panel's installation manual, the SLC manual, and
the Device Compatibility Document.
System Specifications
SYSTEM CAPACITY
• Intelligent Signaling Line Circuits ...........1 expandable to 10
• Intelligent detectors .......................................... 159 per loop
• Addressable monitor/control modules.............. 159 per loop
• Programmable software zones............................. over 2000
• ACS annunciators
per CPU2-3030 .......................32 address x 64 or 96 points
NOTE: The CPU2-3030 can support up to 96 annunciator
address points per ACM-24AT/-48A.
SPECIFICATIONS
Primary Input Power:
– AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum.
– AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum.
DC Output:
– Main 24 VDC: Up to 5.0 A
– Aux 24 VDC: Up to 5.0 A
– 5 VDC: Up to 0.15 A.
Current draw (Standby/Alarm):
– CPU2-3030D board: 0.340 A.
– CPU2-3030ND board: 0.120 A.
– LCM-320: 0.130 A.
– LEM-320: 0.100 A.
firealarmresources.com