Owner's Manual

DN-7070:P • 3/8/17 — Page 7 of 8
on a half-chassis and one NFS2-3030 or NCA-2 mounted on a
half-chassis. The right side houses a microphone/handset
well. The CA-2 assembly includes CMIC-1 microphone. ADDR
Series doors with two-tier visibility are available for use with
the CA-2 configuration: ADDR-B4, ADDR-C4, ADDR-D4
(below).
ADDR-B4: Two-tier-sized door designed for use with the CA-2
chassis configuration. ADDR Series doors are similar to CAB-
4 Series “DR” doors, but a clear window space exposes the
top two tiers of the CAB-4 enclosure. Use an SBB-B4 backbox
with the ADDR-B4. See DN-7045, DN-6857.
ADDR-C4: Three-tier-sized door designed for use with the CA-
2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-C4
backbox with the ADDR-C4. See DN-7045, DN-6857.
ADDR-D4: Four-tier-sized door designed for use with the CA-2
chassis configuration. ADDR Series doors are similar to CAB-
4 Series “DR” doors, but a clear window space exposes the
top two tiers of the CAB-4 enclosure. Use an SBB-D4 backbox
with the ADDR-D4. See DN-7045, DN-6857.
DPA-1: Dress panel, used with the CA-1 chassis when config-
ured with a
DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
DPA-2: Dress Panel used with the CA-2 chassis assembly.
DPA-1A4: Dress panel, used with the CA-1 chassis when the
CMIC-1 is not used. Provides mounting options on right two
bays for two ACS annunciators, or for blank plates. See DN-
7045.
ADP-4B: Annunciator dress plate. Mounts in rows 2, 3 or 4 of
a CAB-4 series enclosure. Used with ACS series annuncia-
tors.
BMP-1: Blank module for unused module positions.
DP-1B: Blank dress panel. Provides dead-front panel for
unused tiers; covers DAA2/DAX series or AA-series amplifier.
BP2-4: Battery plate, required.
CHS-4L: Low-profile four-position Chassis. Mounts two AA-30
amplifiers.
CHS-4N: Chassis for mounting up to four APS-6Rs.
CHS-6: Chassis used with the XP6 and XP10 Multi-Modules.
Mounts up to six modules in any CAB-4 series row.
NFS-LBB: Battery Box. The NFS-LBB is used to mount up to
two 55 AH batteries. Dimensions: Box: 24" (610 mm) wide x
14" (356 mm) high x 7.75" (197 mm) deep. Door: 24.125" (613
mm) wide x 14.25" (362 mm) high; door adds 0.0625" (approx.
1.6 mm) to depth.
BACKBOXES
NOTE: “C” suffix indicates ULC-Listed model.
BB-100: Backbox for batteries and power supplies. The BB-
100 is used to mount up to two 100 AH batteries and power
supply, if needed. 30" (76.20 cm) wide x 25" (63.50 cm) high x
7.5" (19.05 cm) deep; depth includes door.
BB-200: Backbox for batteries and power supplies. Holds up
to four 100 AH batteries (200 AH capacity) and power supply.
30" (76.20 cm) wide x 36" (91.44 cm) high x 7.5" (19.05 cm)
deep; depth includes door.
BB-UZC: Backbox for housing the UZC-256 for applications
where the UZC will not fit in panel enclosure. Black; for red,
order BB-UZC-R. See DN-3404.
ABF-1B(C) Annunciator Flush Box
ABF-1DB(C) Annunciator Flush Box with Door.
UL/ULC Listed.
ABF-2B Annunciator Flush Box
ABF-2DB(C) Annunciator Flush Box with Door
ABF-4B Annunciator Flush Box
ABS-1TB(C) Annunciator Surface Box
ABS-1B(C) Annunciator Surface Box
ABS-2B Annunciator Surface Box
ABS-2D(C) Annunciator Surface Box
ABS-4D(C) Annunciator Surface Box
SEISKIT-CAB: Seismic mounting kit. Required for seismic-
certified applications with NFS2-3030 and other equipment
mounted in CAB-4 Series Enclosures. Includes battery bracket
for
two 26 AH batteries.
SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery
bracket for two 55 AH batteries.
OTHER OPTIONS
411: Slave digital alarm communicator. See DN-6619.
411UDAC: Digital alarm communicator. See DN-6746.
IPDACT-2, IPDACT Internet Monitoring Module: Connects
to primary and secondary DACT telephone output ports for
internet communications over customer-provided Ethernet
connection. Requires compatible Teldat VisorALARM Central
Station Receiver. Can use DHCP or static IP. See DN-60408.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For
mounting an IPDACT-2/2UD onto the panel chassis or CHS-4
series chassis. Use IPENC for external mounting applications.
IPSPLT: Y-adapter option allow connection of both panel dialer
outputs to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT
mounting bracket; Red; for black, order IPENC-B.
IPGSM-4G: Internet and Digital Cellular Fire Alarm Communica-
tor. Provides selectable configurable paths: cellular only, IP only,
or IP primary with cellular backup. Connects to the primary and
secondary ports of a DACT. For Canadian applications order
IPGSM-4GC. See DH-60769.
NOTE: For other options including compatibility with retrofit equip-
ment, refer to the panel's installation manual, the SLC manual, and
the Device Compatibility Document.
System Specifications
SYSTEM CAPACITY
Intelligent Signaling Line Circuits ...........1 expandable to 10
Intelligent detectors .......................................... 159 per loop
Addressable monitor/control modules.............. 159 per loop
Programmable software zones............................. over 2000
ACS annunciators
per CPU2-3030 .......................32 address x 64 or 96 points
NOTE: The CPU2-3030 can support up to 96 annunciator
address points per ACM-24AT/-48A.
SPECIFICATIONS
Primary Input Power:
AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum.
AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum.
DC Output:
Main 24 VDC: Up to 5.0 A
Aux 24 VDC: Up to 5.0 A
5 VDC: Up to 0.15 A.
Current draw (Standby/Alarm):
CPU2-3030D board: 0.340 A.
CPU2-3030ND board: 0.120 A.
LCM-320: 0.130 A.
LEM-320: 0.100 A.