Owner's Manual

DN-7070:P • 3/8/17 — Page 3 of 8
FAPT-851 ACCLIMATE PLUS™ LOW-PROFILE INTELLIGENT
MULTI-SENSOR
Detector automatically adjusts sensitivity levels without
operator intervention or programming. Sensitivity increases
with heat.
Microprocessor-based technology; combination photo and
thermal technology.
Low-temperature signal at 40°F ± 5°F (4.44°C ± 2.77°C).
FSC-851 INTELLIQUAD
A
DVANCED MULTI-CRITERIA DETECTOR
Detects all four major elements of a fire (smoke, heat, CO,
and flame).
Automatic drift compensation of smoke sensor and CO cell.
High nuisance-alarm immunity.
INTELLIGENT FAAST
®
DETECTORS FSA-5000, FSA-8000, FSA-
20000
AND FSA-20000P
Connects directly to the SLC loop of compatible ONYX
series panels.
Provides five event thresholds that can be individually pro-
grammed with descriptive labels for control-by-event pro-
gramming; uses five detector addresses.
Uses patented particle separator and field-replaceable filter
to remove contaminants.
Advanced algorithms reject common nuisance conditions
FSA-5000 covers 5,000 square feet through one pipe.
FSA-8000 covers 8,000 square feet through one pipe.
FSA-20000 covers 28,800 square feet through one to four
pipes.
FSA-20000P covers 28,800 square feet through one to four
addressable pipes. Supports addressable pipes to pinpoint
location of alarm events.
FCO-851 INTELLIQUAD™ PLUS
ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR
Detects all four major elements of a fire.
Separate signal for life-safety CO detection.
Optional addressable sounder base for Temp-3 (fire) or
Temp-4(CO) tone.
Automatic drift compensation of smoke sensor and CO cell.
High nuisance-alarm immunity.
FMM-4-20 GAS DETECTION MODULE
Interface to industry-standard linear scale 4-20 mA sensors.
Five programmable thresholds.
FM Approved, Class 6320 (Stationary Gas Sensors/
Detectors).
SWIFT WIRELESS
Self-healing mesh wireless protocol.
Each SWIFT Gateway supports up to 50 devices: 1 wireless
gateway and up to 49 SWIFT devices.
Up to 4 wireless gateways can be installed with overlapping
network coverage.
RELEASING FEATURES
Ten independent hazards.
Sophisticated cross-zone (three options).
Delay timer and Discharge timers (adjustable).
Abort (four options).
VOICE AND TELEPHONE FEATURES
Up to eight channels of digital audio.
35 watt, 50 watt, 75 watt, and 100/125 watt digital amplifiers
(DAA2/DAX series and DS series).
Solid state message generation.
Hard-wired voice control module options.
Firefighter telephone option.
30- to 120-watt analog amplifiers (AA Series).
Backup tone generator and amplifier option.
FlashScan
®
Exclusive
World-Leading Detector Protocol
At the heart of the NFS2-3030 is a set of detection devices and
device protocol — FlashScan (U.S. Patent 5,539,389). FlashS-
can is an all-digital protocol that gives superior precision and
high noise immunity.
As well as giving quick identification of an active input device,
this protocol can also activate many output devices in a frac-
tion of the time required by competitive protocols. This high
speed also allows the NFS2-3030 to have the largest device
per loop capacity in the industry — 318 points — yet every
input and output device is sampled in less than two seconds.
The microprocessor-based FlashScan
®
detectors have bicolor
LEDs that can be coded to provide diagnostic information,
such as device address during Walk Test.
ONYX Intelligent Sensing
ONYX Intelligent Sensing is a set of software algorithms that
provide the NFS2-3030 with industry-leading smoke detection
capability. These complex algorithms require many calcula-
tions on each reading of each detector, and are made possible
by the very high-speed microcomputer used by the NFS2-
3030.
Drift Compensation and Smoothing. Drift compensation
allows the detector to retain its original ability to detect actual
smoke, and resist false alarms, even as dirt accumulates. It
reduces maintenance requirements by allowing the system to
automatically perform the periodic sensitivity measurements
required by NFPA 72. Smoothing filters are also provided by
software to remove transient noise signals, usually caused by
electrical interference.
Maintenance Warnings. When the drift compensation per-
formed for a detector reaches a certain level, the performance
of the detector may be compromised, and special warnings
are given. There are three warning levels: (1) Low Chamber
value; (2) Maintenance Alert, indicative of dust accumulation
that is near but below the allowed limit; (3) Maintenance
Urgent, indicative of dust accumulation above the allowed limit.
Sensitivity Adjust. Nine sensitivity levels are provided for
alarm detection. These levels can be set manually, or can
change automatically between day and night. Nine levels of
pre-alarm sensitivity can also be selected, based on predeter-
mined levels of alarm. Pre-alarm operation can be latching or
self-restoring, and can be used to activate special control func-
tions.
Self-Optimizing Pre-Alarm. Each detector may be set for
“Self-Optimizing” pre-alarm. In this special mode, the detector
“learns” its normal environment, measuring the peak analog
readings over a long period of time, and setting the pre-alarm
level just above these normal peaks.
Cooperating Multi-Detector Sensing. A patented feature of
ONYX Intelligent Sensing is the ability of a smoke sensor to
consider readings from nearby sensors in making alarm or
pre-alarm decisions. Without statistical sacrifice in the ability to
resist false alarms, it allows a sensor to increase its sensitivity
to actual smoke by a factor of almost two to one.
firealarmresources.com