640-CHARACTER DISPLAY FEATURES
• Backlit, 640-character display.
• Program keypad: full QWERTY keypad.
• Up to nine users, each with a password and selectable
access levels.
• 11 LED indicators: Power; Fire Alarm; Pre-Alarm; Secu-
rity; Supervisory; System Trouble; Other Event; Signals
Silenced; Point Disabled; CPU Failure; Controls Active.
• Membrane Switch Controls: Acknowledge; Signal
Silence; Drill; System Reset; Lamp Test.
• LCD Display: 640 characters (16 lines x 40 characters)
with long-life LED backlight.
FLASHSCAN
®
INTELLIGENT FEATURES
• Polls up to 318 devices on each loop in less than two
seconds.
• Activates up to 159 outputs in less than five seconds.
• Multicolor LEDs blink device address during Walk Test.
• Fully digital, high-precision protocol (U.S. Patent
5,539,389).
• Manual sensitivity adjustment — up to nine levels.
• Pre-alarm ONYX intelligent sensing — up to nine levels.
• Sensitivity levels:
–Ion – 0.5 to 2.5%/foot obscuration.
–Photo – 0.5 to 2.35%/foot obscuration.
– Laser (VIEW
®
) – 0.02 to 2.0%/foot obscuration.
– Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
– IntelliQuad – 1.0 to 4.0%/foot obscuration.
– IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration
• Drift compensation (U.S. Patent 5,764,142).
• Multi-detector algorithm involves nearby detectors in alarm
decision (U.S. Patent 5,627,515).
• Automatic detector sensitivity testing (NFPA-72 compliant).
• Maintenance alert (two levels).
• Self-optimizing pre-alarm.
• Programmable activation of sounder/relay bases during
alarm or pre-alarm.
• Read Status displays the level of detector cleanliness.
FSL-751 VIEW
®
(VERY INTELLIGENT EARLY WARNING)
S
MOKE DETECTION TECHNOLOGY
• Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals (U.S. Patent
5,831,524).
• Addressable operation pinpoints the fire location.
• Early warning performance comparable to the best aspira-
tion systems at a fraction of the lifetime cost.
FRM-1
Relay Contact
NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80 in terminal mode, but not
both at the same time.
CPU2-3030D
display or
CPU2-3030ND
PRN Series
Printer
NFS2-3030
Sample System Options
FAPT-851
FSL-751
FSP-851
FSA-8000
...etc.
Shown in CAB-C4 with display
DVC-EM audio in CA-1 in second tier
7070blok-2013.wmf
LCD-160
LCD2-80
Up to 32
remote
displays
EIA-485
EIA-485
SLC Intelligent Loop
3072 annunciator/control points
Optional 2048-point UDACT
Dual phone
lines to
Central
Station
EIA-232
DEVICES
ACM/AEM-24AT
LED Annunciator
LDM-32
Custom Graphics
ACM-8R
Relay Control
NBG-12LX
XP6/10 I/O Modules
FMM-1
IDC
FWSG