Owner's Manual

Page 2 of 8 — DN-7070:P • 3/8/17
640-CHARACTER DISPLAY FEATURES
Backlit, 640-character display.
Program keypad: full QWERTY keypad.
Up to nine users, each with a password and selectable
access levels.
11 LED indicators: Power; Fire Alarm; Pre-Alarm; Secu-
rity; Supervisory; System Trouble; Other Event; Signals
Silenced; Point Disabled; CPU Failure; Controls Active.
Membrane Switch Controls: Acknowledge; Signal
Silence; Drill; System Reset; Lamp Test.
LCD Display: 640 characters (16 lines x 40 characters)
with long-life LED backlight.
FLASHSCAN
®
INTELLIGENT FEATURES
Polls up to 318 devices on each loop in less than two
seconds.
Activates up to 159 outputs in less than five seconds.
Multicolor LEDs blink device address during Walk Test.
Fully digital, high-precision protocol (U.S. Patent
5,539,389).
Manual sensitivity adjustment — up to nine levels.
Pre-alarm ONYX intelligent sensing — up to nine levels.
Sensitivity levels:
–Ion 0.5 to 2.5%/foot obscuration.
–Photo 0.5 to 2.35%/foot obscuration.
Laser (VIEW
®
) – 0.02 to 2.0%/foot obscuration.
Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
IntelliQuad – 1.0 to 4.0%/foot obscuration.
IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration
Drift compensation (U.S. Patent 5,764,142).
Multi-detector algorithm involves nearby detectors in alarm
decision (U.S. Patent 5,627,515).
Automatic detector sensitivity testing (NFPA-72 compliant).
Maintenance alert (two levels).
Self-optimizing pre-alarm.
Programmable activation of sounder/relay bases during
alarm or pre-alarm.
Read Status displays the level of detector cleanliness.
FSL-751 VIEW
®
(VERY INTELLIGENT EARLY WARNING)
S
MOKE DETECTION TECHNOLOGY
Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals (U.S. Patent
5,831,524).
Addressable operation pinpoints the fire location.
Early warning performance comparable to the best aspira-
tion systems at a fraction of the lifetime cost.
FRM-1
Relay Contact
NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80 in terminal mode, but not
both at the same time.
CPU2-3030D
display or
CPU2-3030ND
PRN Series
Printer
NFS2-3030
Sample System Options
FAPT-851
FSL-751
FSP-851
FSA-8000
...etc.
Shown in CAB-C4 with display
DVC-EM audio in CA-1 in second tier
7070blok-2013.wmf
LCD-160
LCD2-80
Up to 32
remote
displays
EIA-485
EIA-485
SLC Intelligent Loop
3072 annunciator/control points
Optional 2048-point UDACT
Dual phone
lines to
Central
Station
EIA-232
DEVICES
ACM/AEM-24AT
LED Annunciator
LDM-32
Custom Graphics
ACM-8R
Relay Control
NBG-12LX
XP6/10 I/O Modules
FMM-1
IDC
FWSG