Installation Installing Panel Circuit Modules
46 NFS-640 Installation Manual P/N 51332:B2 07/27/2004
Figure 27 Location of D35 on ICM-4RK Circuit Board
3.7.7 Connecting CRM-4RK/CRE-4 Modules
Guidelines for field-wiring the CRM-4RK and the CRE-4:
Provide Form-C relay contacts (silver alloy) used for medium duty switching or pilot duty.
Terminals will accept wire sizes from 12 AWG to 18 AWG (3.1 to 0.78 mm
2
).
Activation of a module or expander relay occurs automatically when an alarm is detected on
a programmed IDC.
UL contact ratings are 5 A at 125 VAC (resistive) or 30 VDC (resistive) and 2 A at 125 VAC
(inductive).
For more information, refer to Section 3.6 “UL Power-limited Wiring Requirements”.
For typical field-wiring connections, refer to Figure 28.
Figure 28 Field-Wiring a CRM-4RK or CRE-4 Module
Cut D35 on the circuit board to
produce California code.
icm-4rk-d35.cdr
CONTROL
RELAY
CONTROL
RELAY
Optional CRE-4 Control
Relay Expander
CREEXPCO-RK.cdr
CRM-4RK
Typical connections for a
Form-C control relay in
normal position.