Instruction Manual
Table Of Contents
- Table of Contents
- Section 1 About This Manual
- Section 2 System Overview
- Section 3 Installation
- 3.1 Preparing for Installation
- 3.2 Installation Checklist
- 3.3 Mounting a Cabinet
- 3.4 Laying Out Equipment in Cabinet and Chassis
- 3.5 Installing the Control Panel
- 3.5.1 Control Panel Circuit Board & Keypad/Display Unit
- 3.5.2 Using NCA as Primary Display
- 3.5.3 Loop Expander Module
- 3.5.4 Network Control Module
- 3.5.5 Panel Circuit Modules and Other Option Boards
- 3.5.6 Overview
- 3.5.7 Connecting the Control Panel to AC Power
- 3.5.8 Checking AC Power
- 3.5.9 Installing and Connecting the Batteries
- 3.5.10 APS-6R Auxiliary Power Supply Connections
- 3.5.11 External DC Power Output Connections
- 3.5.12 NAC Connections & Releasing Circuits
- 3.5.13 Output Relay Connections
- 3.5.14 Backup-Alarm Switches
- 3.5.15 Installing a Transmitter Module TM-4
- 3.6 UL Power-limited Wiring Requirements
- 3.7 Installing Panel Circuit Modules
- 3.8 Auxiliary Relay Module (ARM-4): Product-Specific Details
- 3.9 Installing Remote Printers and/or CRT
- 3.10 Wiring a Signaling Line Circuit (SLC)
- Section 4 Applications
- Section 5 Testing the System
- Appendix A Power Supply Calculations
- Appendix B Electrical Specifications
- Appendix C Compatible Equipment
- Appendix D Canadian Applications
- Index
System Overview System Cabinets
16 NFS-640 Installation Manual P/N 51332:B2 07/27/2004
2.3 System Cabinets
The control panel and modules are installed in a CAB-4 series backbox. There are four different
sizes available, holding from one to four rows of equipment plus batteries (up to two 25AH
batteries). Backboxes are ordered separately from doors. The doors can be mounted on the left or
the right side of the cabinet; reversible hinges are provided so that this choice can be made in the
field. Doors open a full 180 degrees and have locks. Mounting methods include surface-mounting
or semi-flush mounting on a wall between 16 inch (40.64 cm) on-center studs. A trim ring option is
available for semi-flush mounting.
External measurements for each backbox are provided below; door dimensions are larger. Refer to
CAB-3/CAB-4 Series Cabinet Installation Document (shipped with the cabinet) for specific
mounting drawings and door dimensions.
The control panel and adjacent first-row modules mount in chassis CHS-M2, typically in the
first/top row of the backbox. Additional rows of modules can be mounted in chassis CHS-4N
and/or CHS-4L.
Note: If using the new CHS-M2 in a CAB-3 series backbox or in a CAB-4 series backbox
manufactured before October 2002, verify stud height and cut any stud that exceeds 0.375 in.
(9.525 mm) if a CPU is being mounted above it. See warning and instructions in Section 3.5.1
“Control Panel Circuit Board & Keypad/Display Unit”.
Some additional components available in the CAB-4 series include:
Note: When using trim rings, mount backbox with at least 1 inch (2.54 cm) between wall surface
and front of backbox, to allow door to open fully past the trim ring.
A-size backbox
(one row)
24.00 in (60.96 cm) wide
20.00 in (50.8 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-A4
Optional trim ring TR-A4
Opening: 24.062 in (61.118 cm) wide;
20.062 in (50.881 cm) tall.
Molding width: 1.375 in (3.493 cm)
B-size backbox
(two rows)
24.00 in (60.96 cm) wide
28.5 in (72.39 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-B4
Optional trim ring TR-B4
Opening: 24.062 in (61.118 cm) wide;
28.562 in (72.548 cm) tall.
Molding width: 1.375 in (3.493 cm)
C-size backbox
(three rows)
24.00 in (60.96 cm) wide
37.125 in (94.297 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-C4
Optional trim ring TR-C4
Opening: 24.062 in (61.118 cm) wide;
37.187 in (94.455 cm) tall.
Molding width: 1.375 in (3.493 cm)
D-size backbox
(four rows)
24.00 in (60.96 cm) wide
45.75 in (1162.05 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-D4
Optional trim ring TR-D4
Opening: 24.062 in (61.118 cm) wide;
45.812 in (114.775 cm) tall.
Molding width: 1.375 in (3.493 cm)
DP-DISP An Inner Dress Panel for covering the backbox area surrounding display
panels and various modules (required for Canadian installations).
Note: For use with NCA, KDM-2, and primary displays.
BMP-1 Blank Module Plate for covering an unused dress-panel position. Provides
another option for mounting modules such as TM-4, NCM-W, or NCM-F.
BP-4 Battery dress panel
VP-2B or MP-1B
(with DP-1B)
For covering top row(s) of backbox if control panel is mounted in a lower
row. MP-1B is also used to mount panel circuit modules.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com