Instruction Manual
Page 4 of 4 — DN-6972 • 05/01/04
Cable Tray Application Fasteners
Cable Tray Clip
Model Description
CC-2N Will clamp to material from .06 to .16 of an
inch thick and is designed to attach to the
cable tray side rails and secure the
Protectowire in the recommended sine wave
pattern.
CC-2W Will clamp to material ranging from .16 to .25
of an inch thick and is designed to attach to
the cable tray side rails and secure the
Protectowire in the recommended sine wave
pattern.
CC-10N-S The CC-10 Series Clips, are particularly
useful in applications where excessive
vibration may be encountered. CC-10N-S will
clamp to material from .06 to .16 of an inch
thick.
CC-10W-S Are particularly useful in applications where
excessive vibration may be encountered. CC-
10W-S clamps to material ranging from .16 to
.25 of an inch thick.
Spring Clip
Model Description
HPC-2 The HPC-2 contains gripping teeth that will
accommodate mounting sur faces such as
cable trays, storage racks, and ceiling joists.
Pipe Mounting Application Fasteners
Pipe Straps
Model Description
PM-3A These double loop straps suitable for 3/4. to
2. pipe are made of black weather resistant
nylon and may be used in temperatures
ranging from –40ºF (-40ºC) to
185ºF (85ºC).
PM-3B These double loop straps suitable for 2.5. to
3.5. pipe are made of black weather resistant
nylon and may be used in temperatures
ranging from –40ºF (–40ºC) to 185ºF (85ºC).
PM-3C These 2 single loop straps suitable for 4. to 6.
are made of black weather resistant nylon
and may be used in temperatures ranging
from –40ºF (–40ºC) to 185ºF (85ºC).
Messenger Wire Applications
Eyebolt
Model Description
TR-4A Used to attach one end of messenger wire to
supporting structure. TR-4A is steel
construction. TR-4A-S Stainless steel
construction used to attach and tension one
end of messenger wire to supporting
structure.
Turnbuckle
Model Description
TR-24 Used to attach and tension one end of
messenger wire supporting structure.
TR-24-S Stainless steel construction used to attach
and tension one end of messenger wire to
supporting structure.
Typical Class B Protectowire installation using FMM-1 Monitor Module:
ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE
USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
FMM-1
Reference Documention
Install, Operation, and Maintenance
Manual
MAN 2001E-0603
(Found on on www.protectowire.com)
firealarmresources.com