Instruction Manual
Page 2 of 4 — DN-6972 • 05/01/04
Linear Heat Detectors
Models* Temperature Rating
PHSC-155-EPR 155ºF (68ºC) Alarm Temperature
PHSC-155-EPR-M 156-EPR with Messenger Wire
PHSC-190-EPR 190ºF (88ºC) Alarm Temperature
PHSC-190-EPR-M 190-EPR with Messenger Wire
PHSC-280-EPR 280ºF (138ºC) Alarm Temperature
PHSC-280-EPR-M 280-EPR with Messenger Wire
PHSC-356-EPR** 356ºF (180ºC) Alarm Temperature
PHSC-356-EPR-M** 356-EPR with Messenger Wire
*Available in 500 ft. lengths only.
**Maximum Ambient Temperature of 250ºF (121ºC)
CHEMICAL RESISTANCE CHART
FOR PROTECTOWIRE TYPE EPR
JACKET MATERIAL
Ratings-Chemical Effect:
A - Little or no effect. C - Moderate effect.
(< 20% Volume Swell) (40-60% Volume Swell)
B - Minor effect. D - Severe effect - Not
(20-40% Volume Swell) recommended
(>60% Volume Swell)
(Immersion times were approximately 168 hours per ASTM
D-471 at 23°C or as stated.)
Fluids
Chemicals Rating
Acetic Acid 50% A
Sulfuric Acid 98% A
Hydrochloric Acid 10% A
Potassium Hydroxide 10% A
Sodium Hydroxide 50% A
Zinc Chloride 10% A
Water @ 100°C A
Water (Chlorine 4ppm) A
Water (Chloramines 4ppm) A
Sea Water A
Sodium Chloride 15% A
Acetone A
Acrylonitrile A
Aniline A
n-Butyl Acetate A
Ethanol A
Diethylether A
Glycerol A
n-Hexane A
Methanol A
Methylethylketone A
Nitrobenzene A
1- Propanol A
Petroleum Oils & Fuels Rating
Oil ASTM #1 @ 100°C A
Oil ASTM #2 @ 100°C A
Oil ASTM #3 @ 100°C B
Fuel B (Isooctane/Toluene, 70/30) B
Fuel C (Isooctane/Toluene, 50/50) B
Automotive Fluids Rating
Hydraulic Brake Fluid A
Hydraulic Brake Fluid @ 100°C A
Ethylene Glycol A
(Antifreeze/water 50/50) @ 125°C
Approvals/Maximum Listed Spacing
Type EPR Linear Heat Detector
UL (25 ft/7.6m)
FM (25 ft./7.6m)
The distance between detector runs shall not exceed the
listed spacing. Reduced spacing may be required based
upon factors such as ceiling height and construction, physical
obstructions, air movement, or the authority having jur isdiction
(AHJ). When Protectowire is used for sprinkler system
activation, special Factory Mutual (FM) reduced spacing
guidelines may also be applicable.
Important Installation Information. Please Read!
Protectowire Linear Heat Detector may be installed at the ceiling level to protect areas within buildings (area protection) in the
same fashion as the more familiar spot type heat detectors. Please refer to the National Fire Alarm Code, NFPA 72, for basic
information on the installation and spacing of linear heat detectors for area protection. For special applications where the
Detector is installed close to the hazard, the manufacturer’s recommendations and/or installation instructions should be
followed. Whenever there is a choice between two or more possible installation procedures, the one which results in increased
protection should be utilized.
For additional installation information on Protectowire Linear Heat Detectors please refer to the Installation/Operation/
Maintenance Manual (MAN 2001E-0603) and the Important Installation Information document (DS-7736) on
www.Protectowire.com.