Owner's manual

Page 2 of 2 — DN-6870:B1 • 03/27/2012
NOTI•FIRE•NET™ is a trademark, and ONYX® and UniNet® are registered
trademarks of NOTIFIER.. NION® is a registered trademark of Honeywell
International Inc.
NOTIFIER® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
Must be in conduit.
Cannot cross any power lines.
Mounting: The DPI-232 is designed to mount in CHS-M2,
CHS-4N, or CHS-4L chassis; or on the ADP-4B annuncia-
tor dress panel. Refer to the DPI-232 Manual for further
information and diagrams.
Operation Highlights
DIAGNOSTIC LEDS
Power (green LED 1) illuminates to indicate presence of
DC power.
RX Line (green LED 2) illuminates when the RX line is con-
nected to the receiver with proper polarities.
RX 232 (LED 3) when RX Line (LED 2, above), is illumi-
nated, RX 232 (LED 3) illumination indicates data is being
received.
TX 232 (LED 4) when TX Line (LED 5, below), is illumi-
nated, TX 232 (LED 4) illumination indicates data is being
transmitted.
TX Line (green LED 5) illuminates when the TX line is con-
nected to the receiver with proper polarities.
Earth Fault (yellow LED 6) illuminates when a ground fault
is detected on the twisted-pair connected to the transmitter.
SWITCHES AND CONNECTIONS
SW1: Power-Save switch has two settings, “57.6” and
“Low”. Data rates above 9,600 baud require setting the
switch to “57.6” position. Set the switch to “Low” to con-
serve energy for data rates up to 9,600 baud.
•TB1:
–-TX, +TX “Transmit” connections to remote device for use
with 16 – 26 AWG (1.3 to 0.13 mm²) twisted-pair
unshielded wire.
–Earth – connect to ground of cabinet/chassis.
–-RX, +RX “Receive” connections to remote device for use
with 16 – 26 AWG (1.3 to 0.13 mm²) twisted-pair
unshielded wire.
•TB2:
EIA-232 TX – “Transmit” connection to EIA-232 TX con-
nection of panel/peripheral.
EIA-232 REF – “Reference” connection to EIA-232 REF
connection of panel/peripheral.
EIA-232 RX – “Receive” connection to EIA-232 TX con-
nection of panel/peripheral.
Earth Flt (NO, NC, C) – normally open (NO), normally
closed (NC), and common (C) earth fault trouble contacts.
–+24V – connection to listed +24 VDC power source.
– Common – connection to 24 VDC common.
NUP: EIA-232 cable connection for NUP (network) cable
from NUP-compatible equipment.
Agency Listings and Approvals
These listings and approvals apply to the DPI-232. In some
cases, certain modules or applications may not be listed by
certain approval agencies, or listing may be in process. Con-
sult factory for latest listing status.
UL: S635 (Listed for Canadian and non-Canadian
applications).
MEA: 253-02-E.
CSFM: 7300-0028:0222; 7165-0028:0224 (NFS-3030,
NFS2-3030); 7170-0028:0243 (NFS2-640, NFS-320SYS,
NFS-320).
City of Chicago approved; Class 1, Class 2.
City of Denver approved.
FDNY: COA #6085, #6098. #
Product Line Information
DPI-232: Direct Panel Interface modem for extending EIA-232
serial data links.