Instruction Manual
Page 2 of 4 — DN-5566 • 03/30/04
PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,
SPECIFYING, OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS,
CAUTIONS, AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH
TO YOU AND/OR OTHERS.
ORDERING INFORMATION
*Refer to data sheet DN6111 for Mounting Options
NOTE: Due to continous development of our products, specifications and offerings are subject to change without
notice in accordance with Notifier’s standard terms and conditions
MODEL
INPUT
VOLTAGE
VDC
REGULATED
VOLTAGE
RANGE
VDC/FWR
STROBE
CANDELA
(cd)
AS-24MCW 24 16.0 - 33.0 15/30/75/110
AS-241575W 24 16.0 - 33.0 15 (75 on axis)
AS-121575W 12 8.0 - 17.5 15 (75 on axis)
AS-24MCC 24 16.0 - 33.0 15/30/75/95
ASWP-2475W 24 16.0 - 33.0 75 @ -31°F
TABLE 1: RATINGS PER UL 1971
DESCRIPTION V OLUM E
REV ERBERANT
DBA PER UL
464 @ 10 FT.
ANECHOIC
DBA
@ 10 FT.
High 91 99
Medium 88 95
Low 83 90
High 87 99
Medium 84 95
Low 79 90
TABLE 2: DBA RATINGS FOR 12 VDC & 24 VDC SERIES
AS/AH 12 & 24 VDC AUDIBLE
Continuous
Hor n
Code 3 Hor n
ULMEACSFMFMBFP
AS-24MCW-FR 15/30/75/110 X X 24 WALL A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AS-24MCW-FW 15/30/75/110 X X 24 WALL A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AS-241575W-FR 15 (75 on Axis) X X 24 WALL A,B,D,E,F,G,H,J,N,O,R,X X X X X
AS-121575W-FR 15 (75 on Axis) X X 12 WALL A,B,D,E,F,G,H,J,N,O,R,X X X X X
AS-24MCC-FW 15/30/75/95 X X 24 CEILING A,B,D,E,F,G,H,J,N,O,R,X X X X * *
ASWP-2475W-FR 75 @ -31°F X X 24 WALL I X X X X X
A H- 24- R - X X 24 WA LL/CEILING A ,B,D,E,F,G,H,J,N,O,R,X X X X X X
A H- 12- R - X X 12 WA LL/CEILING A ,B,D,E,F,G,H,J,N,O,R,X X X X X X
AH-24WP-R - X X 24 WALL/CEILING K X X X X X
AH-12-WP-R - X X 12 WALL/CEILING K X X X X X
VDC
WALL/
CEILING
M OUNT
M OUNT ING
OPTIONS*
AGENCY APPROVALS
MODEL
STROBE
CANDELA
NON-
SYNC
SYNC
W/SM ,
DSM
NOTES:
SM Sync Module is rated for 3.0 amperes @ 24 VDC.
DSM Sync Module is rated for 3.0 amperes per circuit. The
maximum number of interconnected DSM modules is twenty
(20).
MODEL
NUMBER
INPUT
VOLTAGE
(VDC)
AVERAGE
MEAN
CURRENT
@
24 VDC
MOUNTING
OPTIONS
SM-12/24-R 24 .028 W
DSM-12/24-R 24 .035 W
SYNC M ODELS/POWER SUPPLY
AS devices synchronized with SM Module single Class
“B” (Style Y) circuit
WITH audible silence feature.
WIRING DIAGRAMS
AS device non-synchronized.