ing to 3.5-inch (88.9 mm) octagonal, 4-inch (101.6 mm) octag-
onal, single gang, and 4-inch (101.6 mm) square backboxes
with a square-to-round plaster ring. Wiring connections shall
be made by means of SEMS screws that shall accommodate
14 – 22 AWG wire. The detector shall contain alphanumeric
markings on the exterior of the housing to identify its tempera-
ture rating and activation method. The rate-of-rise element of
combination fixed-temperature/rate-of-rise models shall be
restorable, to allow for field-testing. The detectors shall include
an external collector that shall drop upon activation to identify
the unit in alarm.
ORDERING INFORMATION
WIRING DIAGRAMS
Model*
Identification
Method on
Exterior
Circuit
Temperature
Rating
Activation
UL Protected Spacing,
10’ (3.048 m) Ceiling*
5601P None Single 135°F (57°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m)
5602 Lettering Single 194°F (90°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m)
5603 Lettering Single 135°F (57°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m)
5604 Lettering Single 194°F (90°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m)
5621 Lettering Dual 135°F (57°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m)
5622 Lettering Dual 194°F (90°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m)
5623 Lettering Dual 135°F (57°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m)
5624 Lettering Dual 194°F (90°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m)
NOTE: Refer to NFPA 72 guidelines for spacing reductions when ceiling heights exceed 10 feet (3.048 m).
* Add an “A” to part number for ULC model.
Single-Circuit Models
Dual-Circuit Models
6931wir1.wmf
6931wir2.wmf